Active if Setup Page Lock
(Lockout Menu) is not set to
[hide]
.
604 r/w
0 (or 1.0 if
[dEC1]
is
set to 0.0)
-60.0 to 60.0
[ftr1]
Input Software
Filter 1
Sets the filter time
for the input, in
seconds. This
smooths out a
rapidly changing
input signal.
Positive values
affect the monitor
readings only.
Negative values
affect both the
monitor readings
and the control
values.
Active if Setup Page Lock
(Lockout Menu) is not set to
[hide]
.
606 r/w
0
If Set Sensor Type is
RTD, thermocouple,
(excluding R, S, or B
thermocouple)
[```0]
0(0)
[``)0]
0.0(1)
[dEC1]
Decimal 1
Sets the position of
the decimal point for
input readings.
Active if Setup Page Lock
(Lockout Menu) is not set to
[hide]
.
603 r/w
*
*
[rh`1]
Range High 1
Sets the input range
high. This setting is
the highest value
that the set point
can have.
Active if Setup Page Lock
(Lockout Menu) is not set to
[hide]
.
602 r/w
*
*
[rL`1]
Range Low 1
Sets the input range
low. This setting is
the lowest value
that the set point
can have.
6 . 8
■
P a r a m e t e r s
Wa t l o w S e r i e s 9 7
Setup Page / Input 1 Menu
Display
Parameter
Range
Default
Modbus
Conditions for
Address
Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
*See specifications in the appendix for sensor ranges and defaults.