9
You will need to configure your Gateway with your SMTP server name or address. A DNS server address
must also be configured if using a SMTP name. Contact your system administrator if you don’t know the
SMTP name or address.
Data Logging
The gateway provides no explicit means of data logging. Data can be polled via Modbus TCP by an
external PC program. Consider WatView from Watlow for your setup, data logging and graphing needs.
Control Monitoring and Configuration
The gateway provides a means of monitoring the current process value for analog inputs of each
controller using a built-in HTTP server. It also provides a means of monitoring the present alarm status of
each controller. Additionally, you may monitor and change control set points for control loops of each
controller.
The gateway is capable of supporting Watlow Series 96 non-ramping, 97, 981, 982, 988, 989, 998, 999,
F4S, F4D, F4P, MicroDin, Power Series, CLS200and SD non-ramping controllers with up to 16
controllers in any combination.
The gateway is capable of automatically determining when a controller is connected to the serial bus. It
will identify the model and address of each controller. Controllers with duplicate Modbus addresses will
be ignored by the gateway.
You can configure the baud rate of the EIA-485 or EIA-232 bus. You may also specify which controller
addresses are scanned under the EM Gateway Setup page. The gateway supports from 1 to 16
controllers in any combination of supported model numbers. Select Rescan Modbus Network to update
the detection of controllers on the bus. The Modbus network is automatically scanned every two minutes
for new devices.