54
|
90
Safety Introduction Product Overview
2. Install the inlet side of the manifold towards the water pump.
Important:
Installing the foam manifold at more than a ± 15° tilt may
cause inaccurate readings
.
Top
Figure 44
3. Connect the 3 meter, M12, 4-pin extension cable to the cable attached to
the flowmeter.
Note:
The sensor is calibrated at the factory and secured into place.
Do not rotate the 90° connector attached to the sensor. Doing so
causes inaccurate readings.
Note:
Do not force the plug into the connector, you will damage it.
4. Route the cable to the control box.
5. 3 meter, M12, 4-pin extension cable Connect the cable to the control box.
Refer to:
"Connecting M12 Cables to the Control Box" on page 52
Installing the Flowmeter Tee
1.
Orient the flowmeter with the connector at the top
.
2-1/2-inch tee shown
Figure 45
2.
Install the flowmeter tee into the waterway.
Note:
The flowmeter tee can be installed before or after the waterway
check valve.
3. Connect the 3 meter, M12, 4-pin extension cable to the cable attached to
the flowmeter.
Note:
The sensor is calibrated at the factory and secured into place.
Do not rotate the 90° connector attached to the sensor. Doing so
cause inaccurate readings.
Note:
Do not force the plug into the connector, you will damage it.
4. Route the cable to the control box.