DO NOT START THE SYSTEM UNTIL THE NEXT STEP IS COMPLETE.

Step 9. Complete the Electrical Connection

VectaPure RSX II systems operate using a 120V 15A service and a grounded receptacle.  Insure that 

the power source is rated to the necessary amperage (see page 8) and that the connection meets the 

local electrical code.  See the electrical diagram on page 20.

GROUNDING INSTRUCTIONS

 – This appliance must be grounded. In the event of a malfunction or 

breakdown, grounding will reduce the risk of electric shock by providing a path of least resistance for 

electric current. This appliance is equipped with a cord having an appliance – grounding conductor and 

a grounding plug. The plug must be plugged into an appropriate outlet that is installed and grounded in 

accordance with all local codes and ordinances.

WARNING

 – Improper connection of the appliance – grounding conductor can result in a risk of electric 

shock. Check with a qualified electrician or service representative if you are in doubt whether the 

appliance is properly grounded. Do not modify the plug provided with the appliance; if it will not fit the 

outlet, have a proper outlet installed by a qualified technician.

Section 4: System Set-Up

Set-up of your RO system will be dependent upon the TDS of your feed water.  

Make sure that you 

specify the TDS of your feed water at the time the unit is ordered.

  The system has been shipped 

with a DLFC that will be intended for feed water of less than a TDS of 1000ppm. By changing the DLFC 

the TDS range can be increased up to 2000ppm. See spare parts for range and part numbers when 

ordering an alternate DLFC. 

Make sure that you have the correct waste orifice is fitted to your system.  This orifice has been 

selected to operate at the correct waste flow rate for your system without the need for a waste throttling 

valve.

  

For systems configured for <1000 TDS, the recovery rate will be a maximum of 60%.  For 

systems configured for >1000 TDS, the recovery rate will be a maximum of 35%.

Step 10: Starting Up and Flushing the System

1.  Turn on the feed water valve to the system and check all connections for leaks.  Do not proceed 

further until any leaks are fixed.  Water will flow to the pre-treatment housings but will not pass the 

inlet solenoid (see Figure 5) until the system has been started.  The available line pressure should 

now register on the line pressure gauge. Purge any air from the system by using the red button on 

top of the pre-filter housing.

2.  Open the recirculation valve to the fully open position.

3.  The system pump must be initially primed and at any time that the system has been drained, prior 

to start-up.  THE PUMP MUST NOT BE RUN DRY OR DAMAGE WILL RESULT.  

4.  Once the pump is primed, turn the power switch ON.  Let the system operate for about 5 -10 

minutes with the valve fully open.  The system is now flushing and clearing any dust or debris from 

the lines.  There should be minimal water production from the machine during this process. If the 

unit does produce water, direct this flow to the drain for a period of 60 minutes

Содержание VECTAPURE RSX

Страница 1: ...F RENCE ET DE GUIDE TECHNIQUE IL EST FORTEMENT RECOMMAND DE CONTACTER LE SERVICE TECHNIQUE DE VOTRE REPR SENTANT WATERITE ADVENANT LE CAS D UNE INTERRUPTION INATTENDUE OU BIEN D UNE APPARENTE D FECTU...

Страница 2: ...se retrouver dans le tube Les mol cules des autres min raux et contaminants sont rejet es et vacu es de la surface de la membrane vers le drain Q Quel proc d le Syst me VectapureMC RSX II utilise t i...

Страница 3: ...du syst me OI est lev e plus importante sera la quantit d eau produite par la membrane Votre unit VectapureMC RSX II est munie d une membrane s faible consommation nerg tique qui est con ue pour fonc...

Страница 4: ...lisation continue ou lorsqu utilis avec des sources d eau non trait e Selon la qualit de l eau d alimentation votre membrane s devrait avoir une dur e de vie de 1 5 ans Des conditions d eau plus diffi...

Страница 5: ...rovenir des eaux r siduelles ou de fuites d une fosse septique L eau r siduelle en surface contenant des fertilisants aura aussi une teneur lev e en nitrates La source des nitrates devra tre trouv e e...

Страница 6: ...gmenter la dur e de vie de vos l ments de membrane am liorer la qualit de l eau produite et r duire le temps d entretien et de nettoyage consacr au syst me L importance des conditions de l eau d alime...

Страница 7: ...rie CF Charbon Excelclear pH 5 5 9 5 Corrosion interne Incrustations calcaires dans l quipement Dommages la plomberie Remplacez la source d eau Ajustez le pH Contactez votre d taillant Activit organiq...

Страница 8: ...E DOES NOT RECOMMEND THE USE OF A GRANULAR BLOCK CARBON CARTRIDGE IN THE PRE TREATMENT FILTER HOUSINGS SUPPLIED FOR THE PRIMARY REDUCTION OF CHLORINE IT WILL REQUIRE REPLACEMENT TOO OFTEN LIMIT FLOW R...

Страница 9: ...h If the inlet bulkhead fitting to the non pressurized tank is below the maximum water level in the tank make sure that a check valve is installed in the product water line between the RO unit s outle...

Страница 10: ...Filter Cartridge and Membrane s 1 Remove the filter housing bowl by turning counter clockwise with the housing wrench supplied Remove all protective wrapping from the 5 micron filter cartridge Insert...

Страница 11: ...sure that they are in good condition and are secure in their seating grooves While the housing is disassembled clean all components thoroughly to remove any debris or scaling When re assembling make s...

Страница 12: ...ntial septic field for receiving the RO waste water from Vectapure RSX II systems unless the field has a rated capacity in excess of the waste flow capacity If used to 24 hour capacity these systems w...

Страница 13: ...ded for feed water of less than a TDS of 1000ppm By changing the DLFC the TDS range can be increased up to 2000ppm See spare parts for range and part numbers when ordering an alternate DLFC Make sure...

Страница 14: ...PERIOD A Note on Recovery Rates Your Vectapure RSX II is designed to operate at a recovery rate percentage of product water to total water used at maximum of 60 for feed water of 1000 TDS and 35 40 fo...

Страница 15: ...system pressure feed water TDS permeate TDS permeate flow rate and waste flow rate This will allow you to see any developing performance trends or alert you to system changes that will require you to...

Страница 16: ...parts or repair service during the warranty period Read the document completely for warranty claim instructions Your Vectapure RSX II system comes with a limited one year warranty covering materials...

Страница 17: ...housing leaking Tighten with housing wrench Inspect o rings for cuts or crimps Low System Pressure Clogged pre filter or fouled pre treatment Replace pre filter cartridges Low feed water pressure Chec...

Страница 18: ...oduct Adapter O ring N70209 Membrane Housing End Cap O ring N70328 Pre Filter Housing O ring RKE0013HLB Black Max 2521 Membrane TFC LP BME2521SL Drive Pump 100 GPH APR3BZ Drive Pump 140 GPH APR4BZ Dri...

Страница 19: ...II 350 2 0 USGPM minimum includes 20 safety factor RSX II 700 3 0USGPM minimum on 1000 TDS feed water Feed water must be available at a minimum of 40 psi and a maximum of 80 psi at the specified flow...

Страница 20: ...WATERITE TECHNOLOGIES INC Unit 3 75 Meridian Drive Winnipeg Manitoba Canada R2R 2V9 204 786 1604 Fax 204 7863 1599 waterite waterite com www waterite com Vectapure RSX II Feed Water Quality Waterite...

Страница 21: ...ide Calcium Chloride Iron Fluoride Potassium Bicarbonate Magnesium Sulphate Manganese Nitrate Sodium Phosphate Ammonium Silica Strontium OTHER Total Alkalinity Turbidity Total Dissolved Solids pH Temp...

Страница 22: ...22 REGISTER YOUR PRODUCT ONLINE AT WATERITE COM OR FILL OUT THE INCLUDED PRE PAID SELF ADDRESSED POSTCARD...

Страница 23: ...23 REGISTER YOUR PRODUCT ONLINE AT WATERITE COM OR FILL OUT THE INCLUDED PRE PAID SELF ADDRESSED POSTCARD...

Страница 24: ...24...

Отзывы: