WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL

Water Quality

1.0. Minimum Fluid Volume

A.  Water cooled chillers require a minimum amount of 

source and load side fl uid volume to ensure accurate 
and stable temperatures during system operation. 
For normal air conditioning type applications, it is 
recommended to use at least 7 gallons/ton. 

B.  Applications that require more precise temperature 

control or low loading will occur the minimum 
fl uid volume shall be no less than 10 gallons/ton. 
Installation of a buffer tank that will properly mix the 
fl uid is recommended. 

1.1. Water Cooled Chiller Sizing

A.  Chillers should be adequately sized for optimal system 

effi ciency and run time. Oversizing by more than 15% 
can diminish performance resulting in higher power 
consumption, short cycling of compressors, and 
unstable conditioning temperatures.

B.  In applications where the minimum load is signifi cantly 

less than the design condition, it is better to install 2 
smaller Chillers for load matching rather than a single 
large Chiller.

1.2. Chiller Piping

A.  Multiple Chillers can be installed in series or parallel 

confi gurations. The preferred system design is to pipe 
the equipment in parallel due to its simplicity and 
fl exibility. In parallel systems, the Chiller equipment can 
vary in size as long as fl ow rate and system volume are 
accounted for. 

B.  Piping equipment in series is not desired; however, 

it can be done if proper guidelines are followed. 
Always observe proper temperature and fl ow rate 
requirements for each unit. Sometimes this method is 
desired to achieve larger temperature differences. 

1.3. Strainers

A.  All brazed-plate heat exchangers shall have a 

strainer within 8 ft of the water/brine inlet. It is highly 
recommended to use 30 mesh in order to provide 
maximum fi ltration. In any case, the strainers should 
never have a mesh size larger than 60 or less than 20.

B.  Failure to install proper stainers and perform regular 

service can result in serious damage to the unit, and 
cause degraded performance, reduced operating life 
and failed compressors. Improper installation of the 
unit (which includes not having proper strainers to 
protect the heat exchangers) can also result in voiding 
the warranty. 

C.  Strainers should be selected on the basis of acceptable 

pressure drop, and not on pipe diameter. The strainers 
selected should have a pressure drop at the nominal 
fl ow rate of the units; low enough to be within the 
pumping capacity of the pump being used.

1.4. Flow Sensing Devices

A. A 

fl ow switch or equivalent must be installed on the 

evaporator for each unit to be installed. If the unit is to 
operate as both modes (heating/cooling), a fl ow switch 
is needed on both heat exchangers. 

B.  A differential pressure switch can be used in place of a 

fl ow switch. The differential switch must be capable of 
pressure range as indicated in the pressure drop tables.

1.5. Water Quality

A. 

General:

 Reversible chiller systems may be successfully 

applied in a wide range of commercial and industrial 
applications. It is the responsibility of the system 
designer and installing contractor to ensure that 
acceptable water quality is present and that all 
applicable codes have been met in these installations.

B. 

Water Treatment: 

Do not use untreated or improperly 

treated water. Equipment damage may occur. The 
use of improperly treated or untreated water in this 
equipment may result in scaling, erosion, corrosion, 
algae or slime. The services of a qualifi ed water 
treatment specialist should be engaged to determine 
what treatment, if any, is required. The product 
warranty specifi cally excludes liability for corrosion, 
erosion or deterioration of equipment.

 

The heat exchangers in the units are 316 stainless steel 
plates with copper brazing. The water piping in the 
heat exchanger is steel. There may be other materials 
in the building’s piping system that the designer may 
need to take into consideration when deciding the 
parameters of the water quality.

 

If an antifreeze or water treatment solution is to be 
used, the designer should confi rm it does not have a 
detrimental effect on the materials in the system.

C. 

Contaminated Water:

 In applications where the 

water quality cannot be held to prescribed limits, the 
use of a secondary or intermediate heat exchanger 
is recommended to separate the unit from the 
contaminated water.

 

The following table outlines the water quality 
guidelines for unit heat exchangers. If these conditions 
are exceeded, a secondary heat exchanger is required. 
Failure to supply a secondary heat exchanger where 
needed will result in a warranty exclusion for primary 
heat exchanger corrosion or failure.

 

WARNING: Must have intermediate heat exchanger 
when used in pool applications.

Содержание WC Series

Страница 1: ...n Water Piping Connections Electrical Data Microprocessor Control Startup Procedures Preventive Maintenance WC Series Variable Speed Dual Screw Chiller Installation Manual WC Series Variable Speed Dua...

Страница 2: ......

Страница 3: ...onal Data 9 Rigging Data 12 Center of Gravity 13 Water Quality 14 Water Connections 15 Electrical Data 16 Electrical Connections 16 Wiring Schematics 17 Pressure Drop 20 Electrical System and Controls...

Страница 4: ...knowledging the damage Units are to be stored in a location that provides adequate protection from dirt debris and moisture Units are setup to be side picked using a fork lift Some units include pick...

Страница 5: ...ry Use Only Voltage 4 460 60 3 Electrical Option A Standard Fused Disconnect Control Option B Stand Alone BACnet Non Standard Options SSS None Future Option N Not Applicable Future Option 0 Not Applic...

Страница 6: ...agement control Low impedance line reactors reduce harmonic noise and improve power factor Fused disconnects for each compressor Factory installed flow switches and modulating isolation valves Variabl...

Страница 7: ...nclosure for maximum sound reduction Structural Steel frame to reduce vibration Flange style water connections for an easier and faster connection High efficiency brazed plate heat exchangers for effi...

Страница 8: ...70 21 1 25 3 9 Min Leaving Water 70 21 1 40 4 4 Max Entering Water Brine 133 56 1 80 26 7 Max Leaving Water Brine 140 60 0 70 21 1 Min Differential Temperature 7 3 9 5 2 8 Max Differential Temperatur...

Страница 9: ...9 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Dimensional Data PP PP PP PP PP PP PP PP PP PP PP PP 7RXFK VFUHHQ GLVSOD QVL ODQJH PP PP PP PP DE...

Страница 10: ...10 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Dimensional Data cont PP PP PP PP 92 7 21752 2 1 5 725 2 86 2 2 92 7 2 QVL ODQJH 32 5 1 7 A DETAIL A...

Страница 11: ...RIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Dimensional Data cont RQGHQVHU YDSRUDWRU RPSUHVVRU LOWHU RQGHQVHU 2XWOHW RQGHQVHU QOHW YDSRUDWRU QOHW YDSRUDWRU 2XWOHW LOWHU ULHU LOWHU ULHU...

Страница 12: ...12 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Rigging Data USE SPREADER BARS TO PREVENT DAMAGE OF UNIT...

Страница 13: ...BLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Center of Gravity C D B A F E G hE d t s t s t s Ed Z K Z s dz 1 MODEL SHIPPING WEIGHT NET WEIGHT WCHVE 175 13 000 13 000 WCHVE 225 12 500 12 500 WCHVE...

Страница 14: ...the basis of acceptable pressure drop and not on pipe diameter The strainers selected should have a pressure drop at the nominal ow rate of the units low enough to be within the pumping capacity of t...

Страница 15: ...hould be at least 15 F below the lowest leaving uid temperature Surface Condensation Chart Room Ambient Condition Surface Temperature 50 F 35 F 0 F Normal Max 85 F 70 RH 1 2 3 4 1 Mild Max 80 F 50 RH...

Страница 16: ...0 240 0 20 0 480 0 540 0 600 800 HACR circuit breaker in USA only 7 22 19 1 MCC RLA LRA rating per compressor Breaker FLA sized for both compressors 2 LRA is compressor motor starting current Electri...

Страница 17: ...Y1 EH2 C EH1 C CO C R Off Faul t LED1 R Status LED3 Config LED2 CC2 CC F C R F FG CC CCG CC2 HI CC2 LO CC2 G REVREV FP1 FP1 FP2 FP2 LPS LPS HPSHPS K1 RV Relay K2 CCRelay K3 CC2 Relay K4 Fan Relay K5...

Страница 18: ...ure Use L Output Type CC Dual Single Acc Dip 5 Acc Dip 4 RV B O FP2 15 F 30 F FP1 15 F 30 F 1 2 3 4 5 6 7 8 Off PB2 2 1 3 White 304 White 308 White 312 White 316 Orange 307 Orange 303 Orange 311 Orang...

Страница 19: ...2 DI2 GND L N XO5 X02 1 X02 2 T1 T2 T3 STO STO DI2 DI2 GND L N XO5 X02 1 X02 2 COMP B CONTROL BOARD REACTOR GROUND Transformer 2 24 V PB3 2 1 3 Transformer 3 24 V NOTE 1 460 V 460 V Purple Purple Blac...

Страница 20: ...20 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Evaporator Pressure Drop Condenser Pressure Drop...

Страница 21: ...d to the compressor contactor CC output of the Aurora control Anytime Aurora senses a fault that would require compressor shutdown it will trigger the STO input to turn the motor off High Pressure Swi...

Страница 22: ...er Machine has been Running for 4 Minutes Suction Temperature Discharge Pressure Super Heat Hx1 Gas Pressure Subcooling Hx1 Sat Capacity Hx2 Gas Pressure Return Water from Geo Field Hx2 Sat Hx2 Gas Te...

Страница 23: ...23 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...

Страница 24: ...nds per square inch HC Heating Capacity in MBTUH HE Heat of Extraction in MBTUH kW kilowatt ft hd pressure drop in feet of head HR Heat of Rejection Verify the following High voltage is correct and ma...

Страница 25: ...for debris Check water flow rates and pressure drops across evaporators and condensers Verify graphical data and trending Properly document all data Annual Checks Remove and clean all waterside strai...

Страница 26: ...Total Amps Comp Fan n _____ AMPS n ______ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE...

Страница 27: ...EM OK NG VERIFY ALL REFRIGERANT VALVES ARE OPEN OK NG VERIFY ELECTRICAL PANELS ARE FREE OF FOREIGN MATERIALS AND ALL WIRING IS TIGHT AND SECURE OK NG L1 L2 VOLTAGE V L1 L3 VOLTAGE V L2 L3 VOLTAGE V L1...

Страница 28: ...VAPORATOR LOAD SIDE ANTIFREEZE CONCENTRATION TYPE CONDENSER LOAD SIDE ANTIFREEZE CONCENTRATION TYPE SOURCE LOAD SIDE ANTIFREEZE CONCENTRATION TYPE APPROVAL OF ANTIFREEZE CONCENTRATION TO ADJUST FREEZE...

Страница 29: ...LY ENHANCED CONTROLS ONLY OK NG VERIFY WATER TEMPERATURES CLOSELY MATCH REFRIGERANT SAT TEMPERATURES OK NG VERIFY COMPRESSOR AND UNIT SETTINGS ARE CORRECT SEE SHEET BELOW OK NG COMPUTER STATIC IP ADDR...

Страница 30: ...TER TEMP F ENTERING COLD WATER TEMP F LEAVING COLD WATER TEMP F COMPRESSOR 1 CAPACITY COMPRESSOR AMPERAGE A COMPRESSOR 2 CAPACITY COMPRESSOR AMPERAGE A COMPRESSOR 3 CAPACITY COMPRESSOR AMPERAGE A COMP...

Страница 31: ...31 WC SERIES VARIABLE SPEED DUAL SCREW CHILLER INSTALLATION MANUAL Pages Description Date By All Document Creation July 2019 MA Revision Guide...

Страница 32: ...nd development and reserves the right to change design and speci cations without notice Product WC Series VS Dual Screw Chiller Type Water Cooled Chiller 60 Hz Size 175 300 Tons Document Installation...

Отзывы: