TRUCLIMATE 300 WATER-COOLED CHILLER WITH HYBREX TECHNOLOGY INSTALLATION MANUAL -
Formerly the WC Hybrex Chiller
Chiller Plant with Single Point Disconnect Panel
Wiring Procedures
(Single Point Disconnect Options)
1.
Remove top panels from each chiller to gain clear
access to the high volt wiring path between each
chiller and the single point panel.
2.
Unfold all wire conduit runs and note the label on
each run.
3.
Install the conduit runs support brackets and start
connecting each run to the corresponding breaker in
the single point panel. . Each phase is color coded.
Match the colors to L1, L2 and L3 terminals on the
unit power block or disconnect switch.
4.
Make sure that each wire is properly seated in the
lugs and the lugs are properly torqued.
Recommended torque:
C
DETAIL C
COUNDUIT ROUTING CLAMPS
CONDUIT SUPPORT BRACKET
Figure 28: Single Point Disconnect Power Feed
Breaker Lugs Tightening Torque
Wire
Nm
in-lb
ft-lb
#14-#10
5.6
50.0
4.2
#8-2/0 13.6
120
10
4/0 25.5
225
18.75
9/7/2021