FLOW CENTER INSTALLATION AND LOOP FLUSHING MANUAL
To
Fitting(s)
Rubber Hose Kit
1
" MPT to 1" barbed (PVC or brass)
PVC
1
" MPT to 1" glue socket or 1" MPT nipple
PE
Use brass barbs and double clamp or PE to brass adapter
Copper
1" MPT x 1" sweat and solder before connecting to FC1S, FC2S or 1" MPT nipple
Connection Options
Mounting
The
fl ow center must be mounted with the pump center shaft in the horizontal position. The only adjustment is that the
circulator pump electrical boxes be on the horizontal side of the power head in the mounted position to help prevent mois-
ture from being held inside the box (see Figure 1).
• Side of unit mounting notes:
The fl ow center can be mounted by using
four sheet metal screws directly into the unit
cabinet on the side opposite the air coil. Be
careful not to puncture any internal parts of
the unit when inserting screws into the
cabinet.
•
Unfi nished wall (bare stud) mounting notes:
The assembled fl ow center can be mounted
by using four lag screws into two 19-inch (48
cm) cross braces spanning 16 inches (41 cm)
on center studs or by using lag bolts through
center of brackets into one stud.
• Finished wall (drywall) mounting notes:
The
fl ow center can be mounted by using two
lag screws through drywall into stud through
center holes in top and bottom of cabinet.
Notes:
Insulation should be used on all inside piping
when minimum loop temperatures are expected to be
less then 50° F (10° C). Use table below for insulation
sizes with different piping sizes.
Recommended Insulation
Piping
Description
1
" IPS Rubber Hose
1-3/8
"
ID - 1/2
" Wall
1-1/4
"
IPS PE
1-5/8
"
ID - 1/2
" Wall
2
"
IPS PE
2-1/8
"
ID - 1/2
" Wall
Figure 1: Pump Mounting
Pump mounting and instructions. The pump contains a ceramic impeller
center shaft and is water lubricated. Therefore, shaft
MUST ALWAYS
be
in horizontal position only for proper operation and longevity.
.
OK
OK
Horizontal
OK
NO
Vetical Center
Shaft Position
Vetical Center
Shaft Position
NO
Pumps
MUST ALWAYS
be
mounted so ceramic center
shaft is in horizontal position
ONLY
Rotate pump head so electrical box is on the side or top only. Never leave
electrical box on the botton of pump head (pump windings may short out).
Pumps should never
be mounted in these
positions. The ceramic
center shaft shown is in
the vertical position.
Operating pumps
installed in this manner
will damange the pump.