NSZ/NDZ INSTALLATION MANUAL 

NOTE:

 For closed loop systems with antifreeze protection, set  

SW2-2 to the “loop” position (see DIP Switch Settings table).

Once piping is completed between the unit, pumps and the 
ground loop (see figure below), final purging and charging 
of the loop is required. A flush cart (or a 1.5 HP pump 
minimum) is needed to achieve adequate flow velocity 
in the loop to purge air and dirt particles from the loop 
itself. Antifreeze solution is used in most areas to prevent 
freezing. Flush the system adequately to remove as much 
air as possible then pressurize the loop to a static pressure 
of 40-50 PSI (summer) or 50-75 PSI (winter). This is 
normally adequate for good system operation. Loop static 
pressure will fluctuate with the seasons. Pressures will be 
higher in the winter months 
than during the cooling season. 
This fluctuation is normal and 
should be considered when 
initially charging the system.

After pressurization, be sure 
to remove the plug in the end 
of the loop pump motor(s) (if 
applicable) to allow trapped air 
to be discharged and to ensure 
that the motor housing has been 
flooded. Ensure that the loop 
pumps provide adequate flow 
through the unit(s) by checking 
the pressure drop across the 
heat exchanger and comparing 
it to the unit capacity data 
in the specification catalog. 
Usually 2.5 to 3 GPM of flow 
per ton of cooling capacity is 
recommended in earth loop 
applications.

Figure 7: Typical Split System Application Closed Loop - Earth Coupled

Disconnect

Thermostat Wire
From  Air Handler

Vibration  Absorbing Pad or  Air Pad

P/T Plugs

Lineset
To  Air
Handler

Insulated

Flow Center

Electrical Supply

GeoLink

Flow Center

To Loop

DHW Out

Rubber Hose Connector
Kit CK4L or CK4S

DHW In

Envision to

Electromechanical Units

Shut

Down

C C

SL1

In

SL1

Out

Envision Unit #1

To Electromechanical Unit

C

S

Shut

Down

C C

Shut

Down

C C

SL1

In

SL1

Out

SL1

In

SL1

Out

Single Speed
Envision Unit #1

With pump
wired to Unit 1

With pump
wired to
Unit 2

Envision to Envision

Microprocessor Units

Envision Unit #2
Single Speed

With pump
wired to Unit 1 

With pump
wired to
Unit 2

Shut

Down

C C

Shut

Down

C C

SL1

In

SL1

Out

SL1

In

SL1

Out

Dual Capacity
Envision Unit #1

Envision Unit #2
Dual Capacity

Envision to Envision

Microprocessor Units

Figure 8:  Primary/Secondary Hook-up

Closed Loop - Ground Source Systems

Multiple Units on One Flow Center

When two units are connected to one loop pumping 
system, pump control is automatically achieved by 
connecting the SL terminals on connector P2 in both units 
with 2-wire thermostat wire. These terminals are polarity 
dependant (see Figure 8). The loop pump(s) may be 
powered from either unit, whichever is more convenient. If 
either unit calls, the loop pump(s) will automatically start. 
The use of two units on one flow center is generally limited 
to a total of 20 GPM capacity.

Содержание Envision NDZ Series

Страница 1: ...ons Hot Water Generation Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance IM1003SN 05 10 NSZ NDZ Installation Manual Geothermal Water Source Indoor Split Heat Pump 2 to...

Страница 2: ......

Страница 3: ...e Systems 12 Hot Water Generator Connections 13 14 Electrical Data 15 Thermostat Wiring 15 Wiring Schematics 16 17 Microprocessor Control 18 21 Operation Logic Data 22 DIP Switch Settings 22 Refrigera...

Страница 4: ...59 56 1 59 56 1 59 74 2 1 90 2 55 92 2 61 108 3 06 52 1 47 56 1 59 90 2 55 92 2 61 104 2 95 Coax and Water Piping Water Connections Size Swivel in mm 1 25 4 1 25 4 HWG Connection Size Swivel in mm 1...

Страница 5: ...Model Height Width Depth Water In Water Out Service Valve HWG In HWG Out Low Voltage External Pump Line Voltage Liquid Gas A B C D E F G H J K L M 022 030 19 25 22 50 26 50 1 93 6 93 8 44 11 55 13 43...

Страница 6: ...blower coil units air coils must be installed as specified by the manufacturer s installation instructions however the following recommendations should be considered to minimize noise and service prob...

Страница 7: ...ndlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds Refer to the manufacturer s instructions for the blower coil unit for details on installing the air...

Страница 8: ...T o Thermostat Up Flow Fossil Fuel Furnace Condensate Drain must be trapped A or Slab Coil Supply Duct Air Temperature Limit Switch to prevent compressor operation when entering air is greater than 9...

Страница 9: ...ion Tighten the connectors by hand then gently snug the fitting with pliers to provide a leak proof joint When connecting to an open loop ground water system thread the 1 in MPT fitting SCH80 PVC or c...

Страница 10: ...olenoid Control Valve Rubber Bladder Pressure Tank Lineset T o Air Handler Flow Regulator Shut Off Valves Water Out Water In From W ell Acc Com Acc NC Acc NO 1 2 3 C R P1 P3 SV Solenoid Valve CC GND C...

Страница 11: ...pm Less than 5 ppm Total Dissolved Solids TDS Less than 1000 ppm 1000 1500 ppm 1000 1500 ppm LSI Index 0 5 to 05 0 5 to 05 0 5 to 05 Iron Fouling Biological Growth Iron Fe2 Ferrous Bacterial Iron Pote...

Страница 12: ...lly 2 5 to 3 GPM of flow per ton of cooling capacity is recommended in earth loop applications Figure 7 Typical Split System Application Closed Loop Earth Coupled Disconnect Thermostat Wire From Air H...

Страница 13: ...ot water generator follow these installation guidelines Turn off the power to the water heater 1 Attach a water hose to the water tank drain connection 2 and run the other end of the hose to an open d...

Страница 14: ...e tank 2 Open a hot water faucet in the building to bleed air 3 from the system Close when full Open the pressure relief valve to bleed any remaining 4 air from the tank then close If so equipped unsc...

Страница 15: ...253 26 0 16 6 82 0 29 0 0 4 5 4 22 4 26 6 40 049 208 230 60 1 197 253 33 0 21 1 96 0 34 0 0 4 5 4 26 9 32 2 50 064 208 230 60 1 197 253 40 0 25 6 118 0 41 0 0 4 5 4 31 4 37 8 60 072 208 230 60 1 197 2...

Страница 16: ...CR1 CR2 CR3 CR4 F1and F2 FD HE HP LP PB1 PB2 PS RV SW1 SW2 SW3 SW4 TS Compressor Contactor Condensate overflow sensor DHW pump relay Loop pump relay Fuses Freeze Detection Sensor Heater element High p...

Страница 17: ...sition for pulsed L lockout signal and in the ON position for constant L lockout signal 5 DHW pump only in models with hot water generation option 6 Connection of remote unit that does not have a loop...

Страница 18: ...n control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis Refer to the Field Selection DIP Switch SW2 1 Hot Water High Limit Domestic Hot Wa...

Страница 19: ...The blower starts and operates on low speed Lockout Conditions During lockout mode the appropriate unit and thermostat lockout LEDs will illuminate The compressor loop pump hot water pump and accesso...

Страница 20: ...cription Automatic Reset of Alert Codes Flash Code 1 Long Run Time Thirty alert free on and off cycles to reset automatically Flash Code 2 System Pressure Trip Not applicable Flash Code 3 Short Cyclin...

Страница 21: ...ckout condition text or error number A slow flash of 1 second on and off means the heat pump microprocessor SW2 1 is configured for Test Mode or thermostat is miswired Lockout code 10 see Comfort Aler...

Страница 22: ...econds Loop Protection 15 F Well Protection 30 F 3 Accessory Relay Allows field selection of the accessory relay to operate with the compressor or fan Fan Comp 4 NOT USED N A N A 5 NOT USED N A N A 6...

Страница 23: ...n should be painted with UV resistant paint or covering to insure long insulation life Refrigeration Replace caps after opening system Service ports for attaching refrigerant gauges Insulated Suction...

Страница 24: ...te for the additional 20 ft line set Additional refrigerant to be added 20 ft x 0 5 oz 10 oz Solution 10 oz should be added to the recommended charge of 86 oz found in the Charge Amount with NAH Air H...

Страница 25: ...izes NOTES The Charge Amount with NAH Air Handler column is based on the charge amount for a NAH Air Handler Compressor Section Split Additional charge will have to be added accordingly for line set l...

Страница 26: ...8 5 586 146 5 108 35 4 228 78 1 348 106 7 468 128 8 588 146 8 110 36 4 230 78 7 350 107 2 470 129 1 590 147 1 112 37 3 232 79 2 352 107 6 472 129 4 592 147 3 114 38 2 234 79 8 354 108 0 474 129 8 594...

Страница 27: ...2 Heating No Hot Water Generator Entering Water Temp F Water Flow GPM Ton NSZ022 thru NSZ060 NSZ070 NSZ022 thru NSZ070 Suction Pressure PSIG Discharge Pressure PSIG Suction Pressure PSIG Discharge Pre...

Страница 28: ...2 2 14 8 12 24 39 3 0 145 160 330 360 140 160 375 425 7 17 7 15 4 9 24 39 Second Stage Operation Cooling No Hot Water Generator Entering Water Temp F Water Flow GPM Ton NDZ026 thru NDZ064 NDZ072 NDZ02...

Страница 29: ...6 0 5 7 5 3 4 9 4 6 21 7 8 7 3 6 8 6 4 5 9 10 2 3 2 1 2 0 1 9 1 7 13 3 6 3 3 3 0 2 8 2 6 16 5 0 4 6 4 3 4 0 3 7 19 6 5 6 2 5 8 5 4 5 0 5 30 06 038 full load 049 part load 064 full load 072 part load...

Страница 30: ...ng set point several degrees and 8 verify high speed blower operation Adjust the cooling setpoint above the room 9 temperature and verify that the compressor and water valve or loop pumps deactivate U...

Страница 31: ...suction temperature here at TXV bulb in cooling modes Cooling Cycle Analysis COOLING TXV ACTIVE RIGHT TO LEFT ClgTXV Measure liquid line temperature and pressure here in both heating and cooling mode...

Страница 32: ...it LED NORMAL DISPLAY MODE DIAGNOSTIC MODES CURRENT FAULT STATUS INPUTS OUTPUTS 1 OUTPUTS 2 Field Selection DIPS SW2 1 On SW2 1 Off SW2 1 NA SW2 1 NA SW2 1 NA SW2 6 On SW2 6 On SW2 6 Off SW2 6 On SW2...

Страница 33: ...erated without a filter Obtaining Parts When ordering service or replacement parts refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit If replac...

Страница 34: ...01 TXV 33P609 01 33P609 03 33P609 05 33P609 06 33P609 01 33P609 03 33P609 05 33P609 06 Reversing Valve 33P506 04 33P503 05 33P526 04 33P506 04 33P503 05 33P526 04 Filter Dryer 36P500B01 36P500B02 36P...

Страница 35: ......

Страница 36: ...Manufactured by WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2010 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFu...

Отзывы: