background image

-3-

ELECTROCUTION  HAZARD.  DISCONNECT 

ALL 

ELECTRICAL 

POWER 

BEFORE 

SERVICING.  THE  PRODUCT  MUST  BE  ELECTRICALLY 
GROUNDED. DO NOT INSTALL ON ELECTRICAL SERVICE RATED 
ABOVE 20 AMPS.

WIRING THE DIGITAL CONTROL

1. 

Provide a dedicated, 115VAC / 20A circuit.

2. 

Shut circuit breaker off and verify power is disconnected.

3. 

Loosen screw and remove junction box access cover.

4. 

Route wiring through conduit hole, using proper connector.

5. 

Connect wiring as shown in Figure 2, using wire nuts.

6. 

Reinstall  the  access  cover  and  proceed  to  the  "START-UP" 
section before restoring power. 

START-UP

BEFORE  CONTINUING,  ENSURE  THAT  ALL 
WIRING  IS  COMPLETED  AND  THE  UNIT  IS 

GROUNDED.  CHECK  FOR  OPEN  DRAIN  VALVES  OR  OTHER 
SOURCES OF FLOODING BEFORE STARTING UNIT.

1.  Prime  pump  if  necessary  and  adjust  tank  precharge  to 

manufacturer’s  recommendation  for  intended  pressure  range. 
The factory control setting is 40 psi cut-in and 60 psi cut-out.

2.  Turn  on  power  and  ensure  digital  display  illuminates. 

Display  will  blink  momentarily  and  the  pump  will  start.  If  not,  
check installation.

3.  The display will now read the current water pressure.
4.  Allow the pump to reach the factory cut-off setting of 60 psi. 

IF  THE  PUMP  CANNOT  REACH  THIS  SETTING,  DISCONNECT 
POWER AND SEE “PROGRAMMING THE DIGITAL CONTROL”.

5.  Check for leaks and repair as necessary.

PROGRAMMING THE DIGITAL CONTROL

This  unit  is  factory  programmed  to  turn  the  pump  on  (cut-in) 
at  a  pressure  of  40  psi  and  turn  the  pump  off  (cut-out)  when 
the  pressure  reaches  60  psi.  The  pump  is  capable  of  adding 
approximately  40  psi  to  the  incoming  water  supply  pressure. 
Therefore,  if  the  incoming  water  pressure  is  below  20  psi,  the 
cut-in and cut-out settings require tank precharge adjustment.

Municipal Supply 

Flow Pressure

Cut-In 

Setting

Cut-Out 

Setting

Tank 

Precharge

10 psi

30 psi

50 psi

28 psi

15 psi

35 psi

55 psi

33 psi

20 psi

40 psi*

60 psi*

38 psi*

*Factory default setting

1

.  Press and hold 

. When 

LO

 appears, release. This will determine 

the pressure at which the pump activates.

2

.  When number appears, tap 

  or 

 to change cut-in setting.

3

.  Press 

 again. When 

HI

 appears, tap 

  or 

 to change cut-

out setting. This will determine the pressure at which the pump 
shuts off.

4

. Press 

 a third time. The last Error Code in memory will display 

(see Error Code table in Troubleshooting section). If no errors 
have occurred, the display will show 

- -

5

.  After  approximately  10  seconds 

Pr

  will  appear,  indicating  the 

settings are programmed. Display will then revert to the current 
water pressure.

NOTE:

  The  settings  will  now  be  stored  until  changed  manually, 

even in the event of power failure.

NOTE:

 If pump cannot reach cut-out setting within 5 minutes with 

no water running, lower the pressure settings in 5 psi increments 
to fall within the pump’s pressure capabilities.

PRECHARGE ADJUSTMENT PROCEDURE

Adjust  the  tank  air  precharge  only  at  time  of 
the  digital  control  cut-in  setting  initial 

installation. Water pressure must be relieved to adjust precharge.
1.  Ensure power is off and drain unit to relieve all water pressure.
2.  Remove protective air valve cap.
3.  Release  or  add  air  as  necessary  to  make  the  pre-charge 

pressure 2 psig below the pressure switch pump cut-in setting.

4.  Replace protective air valve cap.

OPERATION

ENSURE  THE  SWITCH  IS  OPERATING  PROPERLY.  AFTER 
MAKING  ANY  ADJUSTMENTS,  OBSERVE  AT  LEAST  ONE  PUMP 
CYCLE TO VERIFY PROPER PUMP SHUT-OFF.

Please contact Water Worker Technical Support at 

844.DIY.TANK

 

if further assistance is required.

Winterizing:

 To drain, disconnect the pump from power and open 

a  faucet  to  bleed  off  water  pressure.  Lay  the  tank  on  its  side  to 
disconnect the piping between the pump and tank to completely 
drain  the  unit.  Ensure  exposed  piping  connected  to  unit  is  
also drained.

DO 

NOT 

ADJUST 

PRESSURE 

OR 

RE-PRESSURIZE  THIS  PRODUCT  EXCEPT 

FOR  ANY  ADJUSTMENTS  MADE  AT  THE  TIME  OF  INITIAL 
INSTALLATION WHEN THE UNIT IS NEW. RE-PRESSURIZATION 
OF A WEAKENED, DAMAGED, OR CORRODED UNIT CAN CAUSE 
AN  EXPLOSION,  POSSIBLY  CAUSING  SERIOUS  OR  FATAL 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.

If pressure adjustments are necessary because of changes in inlet 
pressure, check the condition of the unit first to make sure there 
is no corrosion of the tank or any connected lines or fittings. Take 
appropriate  precautions.  Never  adjust  the  pressure  if  water  is 
leaking from the air stem. Replace any damaged or corroded tank. 
Also, air loss is an indication that damage, corrosion or weakening 
of the unit may have occurred and it should not be re-pressurized.

MAINTENANCE

This  unit,  including  the  pump,  must  be  periodically  inspected  by 
an  experienced    professional  for  signs  of  damage,  corrosion  and 
leaking.  The  pump  should  be  checked  to  ensure  it  is  turning  on 
and off at the appropriate cut-in and cut-out points. At a minimum, 
after installation, a thorough inspection of all components should 
take  place  annually.  However,  note  that  units  in  settings  with 
frequent use, where corrosion, high humidity or aggressive water 
is more likely to occur, and as the unit ages, should be inspected 
more frequently.

Figure 2

Factory Wiring

(Blue & Stripe)

Digital Control

Junction Box

Pump Motor

White (Neutral)

Black (Hot)

115VAC

Line Voltage

Supply

Отзывы: