Operating Parameters
Entering Water
Temp °F
Water Flow
gpm/ton
Cooling
Suction Pressure
psig
Discharge
Pressure psig
Superheat
Subcooling
Water Temp Rise
°F
Air Temp Drop
°F DB
30
1.5
100 - 115
170 - 190
17 - 26
10 - 14
18 - 22
20 - 30
3.0
115 - 125
150 - 170
20 - 29
7 - 11
8 - 10
20 - 30
50
1.5
133 - 148
225 - 245
8 - 11
7 - 11
18 - 22
20 - 30
3.0
129 - 144
185 - 205
8 - 11
6 - 10
8 - 10
20 - 30
70
1.5
139 - 154
300 - 320
6 - 10
6 - 10
18 - 22
18 - 26
3.0
137 - 152
250 - 270
6 - 10
6 - 10
8 - 10
18 - 26
90
1.5
143 - 158
360 - 380
6 - 10
6 - 10
18 - 22
18 - 26
3.0
141 - 156
330 - 350
6 - 10
6 - 10
8 - 10
18 - 26
110
2.3
143 - 158
360 - 380
6 - 10
6 - 10
18 - 22
18 - 22
3.0
141 - 156
440 - 460
6 - 10
6 - 10
8 - 10
18 - 22
Entering Water
Temp °F
Water Flow
gpm/ton
Heating
Suction Pressure
psig
Discharge
Pressure psig
Superheat
Subcooling
Water Temp Drop
°F
Air Temp Rise
°F DB
30
1.5
73 - 79
305 - 330
7 - 13
7 - 11
7 -10
20 - 26
3.0
79 - 85
315 - 345
7 - 13
7 - 11
3 - 6
20 - 26
50
1.5
103 - 109
330 - 370
7 - 13
7 - 11
8 - 11
22 - 32
3.0
115 - 130
350 - 380
7 - 13
7 - 11
4 - 7
22 - 32
70
1.5
145 - 155
375 - 410
7 - 13
7 - 11
11 - 14
28 - 38
3.0
155 - 165
415 - 435
10 - 14
7 - 11
7 - 10
35 - 45
90
1.5
170 - 185
435 - 470
11 - 18
7 - 11
8 - 11
42 - 50
3.0
174 - 190
465 - 500
11 - 18
7 - 11
8 - 11
42 - 50
110
2.3
3.0
NOTES:
Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.
6/20/11
Heating performance based on entering air temperature of 70°F DB.
Operating Limits
Operating Limits
Cooling
Heating
(°F)
(°C)
(°F)
(°C)
Air Limits
Min. Ambient Air
45
7.2
45
7.2
Rated Ambient Air
80
26.7
70
21.1
Max. Ambient Air
100
37.8
85
29.4
Min. Entering Air
50
10.0
40
4.4
Rated Entering Air db/wb
80.6/66.2
27/19
68
20.0
Max. Entering Air db/wb
110/83
43/28.3
80
26.7
Water Limits
Min. Entering Water
30
-1.1
20
-6.7
Normal Entering Water
50-110
10-43.3
30-70
-1.1
Max. Entering Water
120
48.9
90
32.2
NOTE:
Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.