Wärtsilä JOVYSTAR
– DELTA 40 – 150kVA BAX 4647E - 31 -
5.4
Remote Operating Panel
A UPS can be monitored remotely with a remote panel for a distance up to 400m; it can be installed in a control room,
and provides the same user interface as the local panel.
i
NOTE:
Please make sure that 220V-240V, 50/60Hz power supply is available for the remote panel.
The remote operating panel is connected to the RS-485 of the UPS by a shielded cable 4 x 0,5mm, of 400m maximum
length and two DB9 connectors. The cable layout is as follows:
RS485 connection cable
5.5
SNMP-Adaptor
The standard UPS can be monitored by using an SNMP-adaptor. It is provided with two serial interfaces. Interface
COM1 is for communication with the UPS of JOVYATLAS. Interface COM2 is for configuration purposes, for connection
of an additional (special) modem or for MODBUS-applications.
i
CHARACTERISTICS:
- 32-Bit RISC-processor, 8MB-RAM, 4MB Flash
- supported protocols: SNMP, HTTP, Telnet, UPSMON, PPP/ SLIP, SMTP und FTP
- 10/100 Mbit Ethernet-connection
- 2 serial RS-232 Interfaces
- Integrated WEB-Server
- Visualisation by UPSMON, JAVAMON, UNMS, NMS, WEB-Browser or TELNET
- Support UPS-MIB RFC1628
- To be updated through the network
- Fits to all
JOVYATLAS
UPS
The connection of a SNMP adaptor is shown in diagram
X0012400.VP3
in appendix.
5.6
Relay PCB
The relay PCB is used to for transferring alarm and status messages to a remote location.
Alarm PCB no. PB031, layout
The currently used definition of the contacts and LED is at hand on a adhesive label adjacent to the PCB.
1
18
RL1
RL2
RL3
RL4
RL5
RL6
C
N
1
M1
D7 D8 D9 D10 D11 D12
PB031