ELECTRICAL CONNECTION
The heater is designed for permanent connection to a
suitable room thermostat. Please refer to the instructions
of the room thermostat.
ATTENTION
:
If the power cord of the unit is damaged, it
must be replaced immediately.
Fix mounted thermostats should be mounted next to the
heated room’s entry door at 4’ or 1.3m height from floors.
An alternate location is on an interior wall, not subject to
direct sunlight. The thermostat should not be installed
within 3 feet of the LAVA. Power the thermostat with a
GFCI Protected Circuit.
The device is connected with the supplied connector to
a junction box supplying the AC power supply. If a longer
cable is required, it can be replaced by longer one, 18 AWG
or Larger.
HEATING
The heater is controlled by the externally mounted
thermostat.
GROUNDING
The heater is for use with 120 volts. The green-yellow
grounding of the cord must be connected to a permanent
ground inside the junction box.
Installation and Usage Instruction | LAVA® Design Glass Radiator
8
BLACK
WHITE
GREEN GROUND
2” x 4” ELECTRICAL BOX
2” x 4” ELECTRICAL BOX
LAVA Radiant Panel
HOT
LOAD
(black or blue)
POWER
SWITCH
GFCI
Protected
Circuit
Hot
Black
Hot
Black
Neutral
White
Neutral
White
Ground
GROUND
(green or yellow)
NEUTRAL LOAD
(white or brown)
THERMOSTAT
ELECTRICAL BREAKER PANEL
Load
Line
Fig 9: Connection diagram