PELLET STOVES                                                18                                                    PS45 CLASSIC 151211-24

Component Information

The following is a list of other components and their 
functions.

Igniter

The Warmland PS45 stove comes equipped with an automatic 
igniter for lighting the fuel when the stove is in the lighting mode. 
The igniter superheats air that is pulled through the Burn-Pot 
by the combustion blower to light the fuel. The igniter remains 
energized for the fi rst 10 minutes of the lighting sequence.

Vacuum Switch

The stove has a Vacuum Switch, located on the right rear hopper 
leg.  If the pressure drops in the fi rebox due to a leak, a blocked 
fl ue, open front door or unsealed ashdrawer, the vacuum switch 
will sense this and open the circuit to the Auger Motor. The stove 
will then go into a shutdown mode.

Auger and Auger Motor

A 1 rpm  gearmotor turns the Auger, lifting pellets up the 
augertube. The pellets are then dropped down a tube and into 
the burn-pot. The auger is controlled by the control board.

HIGH LIMIT Snap Switch (Manual Reset)

This switch is installed on the convection blower duct and shuts 
the stove down if it senses excessive temperatures (Opens 
at 200° F). This snap switch has a reset button on it and will 
not allow the stove to start up until the reset button has been 
pushed.

Proof of Fire Snap Switch

This switch is installed on the combustion blower and is used to 
sense when there is a fi re in the stove during Start-Up. It will shut 
the stove off if it senses there is no fi re in the Fire-Pot Liner.

Draft Damper

The Warmland PS45 Classic stove has a draft damper located 
at the left side of the stove directly in front of the combustion 
blower. After the stove is installed the Draft Damper will need 
to be set for the vent confi guration. With the stove hot, use a 
magnehelic gauge to adjust the slider until a reading of .15" is 
achieved in the fi rebox. The sampling hole is located in the top 
of the ash box, above the ashpan. To reduce the draft, move 
the adjuster toward the center of the stove.

Burn-Pot Mixer Motor

This 1 RPM gear motor turns the Burn-Pot Mixer rod via a 
coupling and chain drive system.
The Mixer Motor is controlled by the control board.
.

Fig. #20

CLOSED

OPEN

DAMPER: FACTORY
SET, FLUSH WITH
FIREBOX SIDE.

Hopper Switch

The hopper switch is located on the back of the hopper. It is 
activated by the arms of the hopper lid. If the hopper is left open 
it will cut power to the auger motor, the fi re will go out and the 
stove will go into shutdown mode. The #3, head output light 
will also be fl ashing.

Содержание PS45 Classic Series A

Страница 1: ...ur area TESTED and LISTED to ASTM 1509 04 CAN ULC S627 AND UL 1482 IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER SAVE THESE INSTRUCTIONS MODEL PS45 CLASSIC SERIES A SAFETY NOTICE Pleas...

Страница 2: ...n 12 Operation 12 Filling the Hopper 12 Control Board 12 General Operation 13 Thermostat Operation 13 Manual Mode 13 Paint Curing 13 Plated Surfaces 13 Routine Checks and Maintenance 14 Fire Pot and L...

Страница 3: ...smokedetectors Ifyourlocalcoderequiresasmokedetectorbe installedwithinthesameroom youmustfollowtherequirements ofyourlocalcode Checkwithyourlocalbuilding firedepartment for requirements in your area T...

Страница 4: ...tive Pressure Warning This appliance has not been designed to be operated in a negatively pressurized room Provide adequate air for combustion The stove s exhaust system works with negative combustion...

Страница 5: ...pe the clinkers out Clean the holes with a small pointed object if required Refer to the section Routine Cleaning and Maintenance Wood Pellet Specifications This appliance has been designed to burn wo...

Страница 6: ...n meets local building codes It is recommended that the unit be secured into its position in order to avoid any displacement Thisappliancemustbeinstalledonafloorwithan adequate load bearing capacity i...

Страница 7: ...rances removal of the appliance may be necessary for servicing Recommended clearance zone from the front of the appliance to combustibles is 4 feet minimum NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE...

Страница 8: ...60 cm from the edge of the terminal E 12 inches 30 cm Clearance to unventilated soffit F 12 inches 30 cm Clearance to outside corner G 12 inches 30 cm Clearance to inside corner H 3 feet 90 cm Not to...

Страница 9: ...e or odor during appliance shut down or power failure and avoid exposing people or landscaping shrubs to high temperatures Hooded vent Using existing wood vent Thru roof Recommended Recommended Recomm...

Страница 10: ...e are approved however it is recommended that a minimum of 5 ft of vertical be included in the vent system Having a vertical section in the venting will help prevent smoke from exiting the appliance d...

Страница 11: ...this safely all sections of listed connector offset elbows and chimney section must be screwed to gether by at least three sheet metal screws per joint The chimney must be suitably supported by the ch...

Страница 12: ...rers instructions could result in a malfunction Pay special attention to the thermostat location requirements If the location requirements are not followed the appliance may operate erratically or fai...

Страница 13: ...un out of pellets the auger will be empty and the Burn Pot liner will need to be primed To prime place a handful of pellets into the middle of the liner On the control board push the ON OFF button Thi...

Страница 14: ...ning brush can be used to loosen any ash build up before vacuuming DONOTUSEASTANDARDHOUSEHOLDVACUUM WHEN USINGA SHOPVACUUM A FINE DUST FILTER MUST BE INSTALLED AS THE STANDARD FILTERS WILL LEAK THE FI...

Страница 15: ...ut the Ash Pan enclosure before inserting the Ash Pan Fig 11 CAUTION Disposal of Ashes Ashes should be placed in a metal container with a tight fitting lid The closed container shouldbeplacedonanon co...

Страница 16: ...clean out all the ash in the exhaust passages Fig 17 Fig 16 Don tforgettocleanuparoundtheheatexchanger Oncetheflue passage is clear of ash build up reinstall the Firebox Liner Fig 17 Firebox Passage C...

Страница 17: ...Fig 19 Cleaning the Convection Blower To clean the convection blower remove the right cabinet side see previous page Disconnect the stove power cord from the electrical outlet Using a 3 8 wrench remo...

Страница 18: ...reset button on it and will not allow the stove to start up until the reset button has been pushed Proof of Fire Snap Switch This switch is installed on the combustion blower and is used to sense when...

Страница 19: ...PELLET STOVES 19 PS45 CLASSIC 151211 24 Wiring Diagram 5050 838 A 010210 PS 45 WIRING...

Страница 20: ...25 1 5068 7173 VENT STARTER TUBE GASKET 26 1 PS45 7384WLD VENT STARTER TUBE 27 1 5027 171 EXHAUST TEMPERATURE SWITCH 28 1 5024 503 COMBUSTION BLOWER 29 1 PS45 7415XXX SIDE SHIELD LEFT RIGHT 30 1 PS45...

Страница 21: ...PELLET STOVES 21 PS45 CLASSIC 151211 24 a a b b Components List A B...

Страница 22: ...PELLET STOVES 22 PS45 CLASSIC 151211 24...

Страница 23: ...PELLET STOVES 23 PS45 CLASSIC 151211 24 Rating Label...

Страница 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD www pacificenergy net 2975 Allenby Rd Duncan BC V9L 6V8 Technical Support 250 748 1184...

Отзывы: