Figure 2.27
Cascade Chimney Connection in the Attic with Concentric (Ø100/150mm) Chimney Sets
Concentric (Optional) Chimney Accessories (Ø100/150 mm) for VIWA 90, 115, 125 and 150 Wall-Mounted Condensing Boilers
2.7.3. Mounting with Concentric Chimney Sets in The Attic
In the cascade installations in the attic, waste gas chimney connection
of each boiler can be done with concentric (Ø100/150mm) Horizontal
or Vertical Chimney Sets. This is in accordance with TS 7363.
Baca aksesuarları birbirlerine sıkı geçme ile yöntemi ile monte edilebilir ve bu nedenle bağlantı için ek bir paçaya gerek yoktur.
Product Code
Product Name
Product Explanation
Product Image
153.11.014.000007
Ø 100/150
Horizontal
Chimney Set
Maximum Chimney
Distances
Lmax= 18 m (Viwa 90)
Lmax= 17 m (Viwa 115)
Lmax= 17 m (Viwa 125)
Lmax= 10 m (Viwa 150)
153.11.660.600042
Ø 100/150 Extension
Chimney
L=500 mm
Can be used with Horizontal Chimney Set and
Vertical Chimney Set.
153.11.660.600043
Ø 100/150 Extension
Chimney
L=1000 mm
Can be used with Horizontal Chimney Set and
Vertical Chimney Set.
153.11.660.600040
Ø 100/100
Flue Check Valve
This is an accessory that must be installed at the
outlet of each boiler when multiple boilers are used
in the cascade system.
153.11.660.600068
BOB 100.100
Flue Check Valve
If more than one boiler is used in the cascade
system, Non-angled flap accessories must be
inserted on to each boiler's flue outlet. The boiler
connection and the collector connection are Ø100
mm
153.11.660.600044
Ø 100/150 Elbow
(90°)
Can be used with Horizontal Chimney Set and
Vertical Chimney Set. Each 90° elbow use
requires a reduction of 100cm from the maximum
horizontal/ vertical distance.
153.11.660.600041
Ø 100/150 Vertical
Chimney Set
Maximum Chimney
Distance
Lmax= 20 m (Viwa 90)
Lmax= 20 m (Viwa 115)
Lmax= 19 m (Viwa 125)
Lmax= 11 m (Viwa 150
The chimney accessories can be mounted each other by close-fit method, so there is no need for an additional part for the connection.