background image

 

Page 

5

 of 

9

 

4  INSTALLATION 

4.1  Cylinder Location 

The unit must be located where it can be supplied from an expansion tank / cistern above the 
cylinder.  A vertical vent pipe of at least 19mm internal diameter must be connected to the hot 
outlet. 

Ensure  the  cylinder  is  positioned  such  that  future  servicing  and  part  replacement  is  possible.  
The  routing  of  pipework  must  not  prevent  the  thermostats  or  immersion  heater  from  being 
removed for maintenance. 

4.2  Hot & Cold Water Connections 

All connections to the cylinder must be made using compression fittings. We recommend 22mm 
supply pipework is used. 

4.2.1  Drain 

A full bore drain cock (not supplied) must be fitted to the cold inlet pipework, between the cistern 
and the cylinder, at as low a level as possible, to facilitate draining. 

4.2.2  Distribution pipework 

The  pipework  supplying  the  hot  water  taps  should  be  run  in  22mm  throughout  the  property.  
Only short lengths (max 1 metre) of 15mm should be used to connect baths, showers and basin 
taps  where  required.    If  using  a  secondary  /  pumped  return  circuit,  all  pipework  must  be  well 
insulated. The circulator (bronze pump) should be time and/or temperature controlled to reduce 
energy consumption. 

4.3  Primary, Renewable & Tertiary Circuits 

The working pressure and temperature for all heat exchanger coils must not exceed 6 bar and 
120°C respectively.  All connection to the cylinder must be made using compression fittings. 

All 22mm coils 

must be fully pumped

 – gravity circulation is NOT suitable for the 22mm coils. 

Gravity  circulation  may  be  used  on  the  28mm  coil(s)  only,  although  these  may  be  pumped  if 
desired. 

4.3.1  Safety thermostat 

Each heat exchanger coil has an associated combined control & safety thermostat.  These can 
be used as part of system controls on 

fully pumped circuits only

.  Suggested S-Plan and Y-

plan system schematics are given in Section 4.5. 

Controls devises (e.g. motorised valves) 

must not be used on gravity circuits

4.3.2  Solar installations 

If connecting a solar thermal installation, for example, to the renewable coil, the controls must 
be wired in series with the combined control & safety thermostat.  If using a solar pump station 
with check valves to prevent gravity circulation, a motorised valve may not be required.  Refer to 
the  appliance  manufacturer’s  instructions  and  to  Building  Control  for  further  guidance.  
Additional motorised valves (not supplied) may be required. 

4.4  Hard water 

In areas with moderately hard water, choosing a lower control thermostat temperature can result 
in  less  scale  being  deposited  within  the  cylinder.    Where  water  hardness  in  excess  of 
200mg/litre is experienced, a suitable and effective hard water treatment must be installed.  A 
devise  rated  for  a  flow  rate  of  50  litres  per  minute  is  recommended  in  order  to  maintain 
maximum performance. 

 

Содержание TW180V

Страница 1: ...tallation Instructions Guarantee Registration Open Vented Cylinders Stainless Steel Water Heaters Products covered by this manual Twin Coil TW180V TW210V TW250V TW300V Triple Coil TR250V TR300V LEAVE...

Страница 2: ...il at the addresses below Please also refer to our website Should replacement components be required a list of available spares is provided in Section 5 2 page 8 In the unlikely event that replacement...

Страница 3: ...g the immersion cover All cylinders are supplied with an immersion heater to allow the cylinder to be heated electrically The immersion heater has an immersion thermostat the temperature of which is a...

Страница 4: ...ewable coil upper connection mm 532 532 532 532 F Cold inlet connection mm 482 482 482 482 G Renewable coil lower connection mm 432 432 432 432 OPERATING DATA Cold water capacity litres 180 210 250 30...

Страница 5: ...e coil upper connection mm 462 532 H Cold inlet connection mm 412 482 J Renewable coil lower connection mm 362 432 OPERATING DATA Cold water capacity litres 248 298 Weight when full kg 290 350 Standin...

Страница 6: ...ils must not exceed 6 bar and 120 C respectively All connection to the cylinder must be made using compression fittings All 22mm coils must be fully pumped gravity circulation is NOT suitable for the...

Страница 7: ...rough the base then insert downwards into the pocket as shown in Figure 5 Anchor the cable using the clamp provided Figure 5 Solar temperature sensor installation Main lower solar sensor location Twin...

Страница 8: ...Thermostat Mid position Valve 5 Amp Fused Spur Isolator Live L Neutral N Earth E Heating On X Hot Water On Y Hot Water Off Z L N E N N N N N N N N N 2 E E E E L L L X Y 1 3 L G N E 3 2 B E O N G L E O...

Страница 9: ...sible cause Possible remedy Little no hot water flow Mains water supply isolated Open stopcock Cistern ball cock failure Check ball cock in cistern tank Water from hot taps is cold Boiler programmer o...

Страница 10: ...e case of defects arising from normal deterioration or improper or faulty handling or processing of the unit by the customer 2 4 consequential losses however caused 3 If within the 2 year guaranteed p...

Отзывы: