71
Subject to error and alteration
Technical Data
#57838
General data
Housing:
Plastic enclosure
90 x 116 x 56 mm (LxWxH)
Weight:
approx. 330g
IP enclosure rating:
IP 20
Installation orientation:
any
Fastening / mounting:
DIN rail 35mm
Battery:
CR 1632
Battery life:
min. 10 years
Ambient conditions
Working temperature range:
0°C - 57°C
above an ambient temperature of 47°C the permis-
sible switching current is reduced (see Derating)
Storage temperature range:
-25°C - 70°C
Relative humidity:
5..95% rH
(non-condensing)
Pollution degree:
2
Operating altitude:
0 .. 2000m above sea level
Ventilation:
No external ventilation required
Electrical data
Supply voltage:
110 - 230V AC, 50/60Hz
Current draw:
150 - 50 mA
Over-voltage category:
Category II
Protection class:
I
Galvanic isolation:
Digital output - Network: min. 2000 V
Digital input - Network: min. 2000 V
Digital outputs:
Four relay potential-free change over contact
Four relay potential-free normaly open contact
AC1: 16 A / 250 V AC
AC15: 3 A / 120 V 1.5 A / 240 V
AC3: 750 W
DC1: 16 A / 24 V DC
DC13: 0.22 A / 120 V 0.1 A / 250 V
max. 1800 switching cycles per hour
Network:
10/100BaseT autosensing
Connections
Network:
RJ45