Wander Control Systems KP-1 Скачать руководство пользователя страница 5

Wander Control Systems, Inc. 

 

WCSI Keypad Installation Manual   Page 5 of 6 

Mounting 

 

1)  The remote access panel which has been chosen for this location is to be 

mounted beside the door on the opposite side of the wall from the door 
controller (Platinum 3, Platinum 3B, or Sentry). 

 

2)  Mount the remote access panel close to the door in a convenient location at 

approximately 4 ½ feet from the floor.  Mark a precise location for mounting 
and drill through the wall. 

 

(If necessary, wires may be run through a Wiremold channel mounted 
vertically, but an access hole must be drilled through the top of the surface 
mount box.) 

 

4)  Screw surface mount box (backbox) to the wall.  (The backbox must be 

securely attached to the wall). 

 

5)  After the backbox has been securely fastened to the wall you may pull the 

wires to the box from the door controller. 

 
 

Set-up Connections 

 

KP-1 & KP-2 

 

There are 3 wires used on the KP-1 & KP-2.  The colors and functions are as follows: 

 

Red   

- Positive Power (6 

– 12VDC) 

Black   

- Common Ground 

Green  

- Output  

 
 

We recommended that you use 18 - 4 stranded wire 

because you need to run three wires from the 

Platinum 3, Platinum 3B or Sentry control unit out to 

the KP-1or KP-2 remote access panel. 

 

 
 

Connect the three wires from the controller to the KP-1 or KP-2 remote access panels 
as follows: 

 

KP-1 & KP-2  

 

Platinum 3, Platinum 3B or Sentry Controllers 

 

Red 

 

 

 

 

J5 

– Pin 1 – +12VDC 

Black   

 

 

 

J5 

– Pin 2 – Ground 

Green   

 

 

 

J3 

– Pin 2 – Escort Trigger In 

 
 

Platinum 3, Platinum 3B, or Sentry controller J3 Pin 1 is NOT 

used in connecting a remote access panel. 

Содержание KP-1

Страница 1: ...stems Designed KP 1 KP 2 EscortR ONLY Accessories for Platinum 3 Platinum 3B Sentry Door Control Systems Wander Control Systems Inc 210 Richlandtown Pike Quakertown PA 18951 Telephone 215 538 1983 After Hours 407 446 0055 www wandercontrol com ...

Страница 2: ...tion Manual Page 2 of 6 Table of Contents Installation 3 Overview 4 Recommendations Wire Sizes 4 Tools 4 Wiring Strategy 4 Mounting 5 Set up Connections KP 1 KP 2 to Door Controllers 5 EscortR 6 FAQs 6 Figure Figure 1 Platinum 3 Installation Diagram 3 ...

Страница 3: ...nc 3 WCSI Keypad Installation Manual Page 3 of 6 KP 1 KP 2 EscortR Installation Manual Installation Figure 1 Platinum 3 Installation Diagram Note Diagram depicts a Platinum 3 with an antenna The Sentry does NOT have an antenna ...

Страница 4: ...or wire requirements and other regulations Wire Sizes Suggested It is recommended to use 18 4 AWG stranded PVC coated low voltage wire from each door controller to each KP 1 KP 2 or EscortR remote access panel Tools Suggested minimum Screw Drivers Flat Phillips Wire Strippers Drill Drill Bits Volt Meter Wire Cutters Once you have evaluated your Wander Control Systems Inc equipment components and r...

Страница 5: ...ll The backbox must be securely attached to the wall 5 After the backbox has been securely fastened to the wall you may pull the wires to the box from the door controller Set up Connections KP 1 KP 2 There are 3 wires used on the KP 1 KP 2 The colors and functions are as follows Red Positive Power 6 12VDC Black Common Ground Green Output We recommended that you use 18 4 stranded wire because you n...

Страница 6: ...ntry controller 3 Connect wire from hole A to appropriate hole for first numeral of escort code 4 Repeat with wire from hole B to appropriate hole for second numeral of escort code Repeat with wires C D E as necessary Can I use repeat digits in my code No unique digits only i e 12345 Do not use the same numeral twice in your escort code Do NOT use the numeral 9 in your code If you change the escor...

Отзывы: