OVERVIEW

The LDS-700 is a dual technology line voltage wall switch 
sensor in the IR-TEC’s WALLSENZR family designed to fit 
in a standard NEMA wall box for energy efficient automatic 
load control. This state-of-the-art wall switch sensor 
combines digital Passive Infrared (PIR) and advanced High 
Frequency Doppler (HFD) sensing technologies into an 
aesthetically pleasing housing to provide second-to-none 
occupancy/vacancy sensing performance within its 180° 
field of view detection range. 

The sensor is factory set to turn ON the load automatically 
when PIR sensor detects the presence of an occupant, 
and will turn OFF automatically if no motion is detected by 
either PIR or HFD sensor before the delay time elapses. To 
comply with specific energy code, such as CA Title 24, the 
LDS-700 series can be easily programmed to operate as a 
Vacancy Sensor. In vacancy sensing mode, the sensor will 
only turn ON the load by pressing the push-button 
manually and will turn OFF the load automatically as per 
sensor delay time set. Various sensing operation and 
control modes can be achieved by different DIP switch 
setting combinations and push-button operations.

INSTALLATION NOTES

SPECIFICATIONS 

Line Voltage Dual-Tech Wall Switch Sensor

INSTALLATION INSTRUCTIONS

LDS-700 Series

Power supply
Sensing technology

Inrush current
Load switching
Detectable speed
Mounting height

Ambient light level
Delay time setting
Op. humidity
Op. temperature
Dimensions

Detection coverage

Maximum load

120/277VAC, 60Hz
Digital PIR & High Frequency Doppler
Incandescent/Halogen – 800W (VA)
Fluorescent Ballast/CFL – 800W (VA)

Ballast Electronic (LED) – 500/800VA@120/277V
Motor – 1/6 HP 
Max. 80A, 16.7 ms @60Hz
Zero-cross Hybrid-Switching 
1~10 ft./sec. (0.3~3 m/sec)
3~5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft high
Minor motion - 20 ft x 20 ft (W x L) @4 ft high
7 levels, from dark to 24 Hour
T/1’/3’/5’/10’/20’/30’, T=10 sec. for testing 
Max. 95% RH, non-condensate
-40°F ~ 131°F (-40°C ~ 55°C)
4.13”H x 1.77”W x 1.65”D (w/mounting plate) 

INDOOR USE ONLY
Utilisation a L'interieur Uniquement

Risk of Electric Shock - Disconnect power supply at the circuit breaker 

before installing, replacing lamps, or servicing.
DO NOT 

control a load in excess of specified ratings to avoid damaging the 

sensor or the property. 
Install and use this sensor in accordance with electrical codes and regulations.

 

This device is intended to be installed by a qualified electrician. 

DO NOT

 

attempt to service or repair.

Afin d'eviter tout risque de choc electrique ou electrocution, couper le 

courant au disjoncteur avant installation, remplacement des lampes ou 

tout service d'entretien.

NE PAS contrôler une charge supérieure à la capacité spécifiée pour éviter 

d'endommager le capteur ou la propriété.
Installer et utiliser ce capteur conformément aux codes et règlements 

électriques.
Ce dispositif est destiné à être installé par un électricien qualifié. NE PAS 

tenter de réparer.

The sensor is more sensitive to the movements 
“crossing” the detection zones than “toward” or “away” 
the sensor. To obtain better sensitivity, ensure the sensor 
to have clear field of view for the occupant’s motion 
within the desired coverage. 

The closer movement is to the sensor, the more 
sensitive the sensor is. 

The sensor should be mounted within the specified 
mounting height for optimal performance. 

Avoid blocking the sensor with any obstacles, such as 
door, plant, partition or furniture. As a general rule, every 
occupant within the desired range should be able to 
clearly see the sensor.

Do NOT mount the sensor directly above or nearby a 
heat source, or where unintended motion (e.g. hallway 
traffic) will be “seen” by the sensor. 

1.

2.

3.

4.

5.

DETECTION COVERAGE

40’

Top view

Side view

4’

7’

30’

40’

Minor motion

20’

20’

Major motion

180°, 30 ft x 40 ft (W x L)

This device complies with Part 15 of the FCC Rules.  

Operation is subject to the following two conditions:

(1)This device may not cause harmful interference,

(2)This device must accept any interference received, 

Including interference that may cause undesired operation.

FCC NOTICE

P/N: 058-70004-003

Printed in Taiwan

www.irtec.com

This product may be covered by one or more U.S. patents or patent applications.

Please visit www.irtec.com for more information.

WARNING & CAUTION

AVERTISSEMENT & PRUDENCE

Install the sensor at least 1ft. away from any occupant.

Отзывы: