Thermal process
safeguard opened:
Air in the system.
Pump hanged up.
A valve in the circuit is closed.
Controller with false settings or
faulty.
Close the primary air (Push the primary air level to
- ).
If installed: The WAL03 controller will close the el.
air flap when the water temperature raises up to
90°C.
Keep closed the doors.
Keep calm.
Kein Holz mehr nachfüllen.
Do not load more wood, the thermal process
safeguard come into force. As soon as the
electricity is back, please check the following:
A)
Pressure, at least 1,5 bar
B)
Bleed the system
check the pump (set the thermostat at 0° C and
check if the pump starts to work, afterwards set it
again at 60° C)
How to cool the storage tank if it is heated up completely ( >80°C).
Storage tank
completely at a
temperature >80°C
No water consumption, no heating
system activated.
Boiler stove in function whilst the
storage tank was at high temp.
A second heat source works at the
same time as the boiler stove.
a)
Start the pump of the room heating system.
b)
Use hot domestic water.
9 Legal information:
9.a General information
Information
If there is an exchange of information with the boiler stove manufacturer, please quote
the serial number and identification data, which you will find on the stove’s label.
Liabilities
Upon delivery of this manual, Wallnöfer GmbH declines all liabilities, both civil and penal,
for any accidents that may derive form the total or partial failure to comply with the
specifications contained in it.
Wallnöfer GmbH also declines all liabilities resulting from an improper use of the
stove, incorrect use by the user or resulting from unauthorized alterations and/or
repairs, or the use of spare parts that are either not genuine or not specific for
this particular model.