4.1 Technical details: Electrical connection-conditions
Electrical connection-conditions
Model
wallbe Eco 2.0
3,7kW
wallbe Eco 2.0
4,6kW
wallbe Eco 2.0
7,4kW
wallbe Eco 2.0
11kW
wallbe Eco 2.0
22kW
Input terminal
X1
L1/N/PE
X1
L1/N/PE
X1
L1/N/PE
X1
L1/L2/L3/N/PE
X1
L1/L2/L3/N/PE
Supply line
NYM-J
3x2,5mm²
NYM-J
3x2,5mm²
NYM-J
3x6mm²
NYM-J
5x2,5mm²
NYM-J
5x6mm²
LS_switch/
preliminary fuse
1 pol. x C 16A
1 pol. x C 20A
1 pol. x C 32A
3 pol. x C 16A
3 pol. x C 32A
RCD in switch
board
RCD Typ A
A0,03A/25A
RCD Typ A
A0,03A/25A
RCD Typ A
A0,03A/40A
RCD Typ A
A0,03A/25A
RCD Typ A
A0,03A/40A
4.
Be aware
that you have to install an adequate LS-switch (see table) in the
subdistribution!
5.
Be aware
that your wallbe Eco 2.0 is already equipped with a DC residual current
detection >6mA. Therefore a cost intensive RCD Type A (EV) or Type B in the switch
board is not necessary.
6.
We recommend
the integration of an overvoltage protection device in the switch
board.
7.
We strongly advise you to follow local norms and regulations.