Gas Conversion and Specifications
Commissioning
Before leaving the installation;
1. Check all gas connections for leakage using soapy water or other gas detecting equipment.
2. Carry out a ‘Commissioning’ check of appliance as shown in Installation Section of this manual.
3. Ensure any adjustments done to components that have adjustments / settings paint sealed are to be
re-sealed.
Gas Specifications
-
Australia / New Zealand Only:
-
UK Only:
Appliance Classification
Category:
II
2H3P
(20, 30 / 37).
Flue Type: A
1.
*
- Measure burner operating pressure at manifold test point with two burners operating at full
setting. Operating pressure is ex-factory set, through appliance regulator and is not to be
adjusted, apart from when carrying out Gas Conversion, if required. (Refer to ‘Gas Conversion’
section for details).
D
O
NOT
USE
A
NAKED
FLAME
TO
CHECK
FOR
GAS
LEAKAGES
.
Warning
Natural. Gas
LP Gas (Propane)
Open Burner
Main Burner Injectors
Ø 2.45 mm
Ø 1.50 mm
Pilot Burner ('PF' Option Only)
0.30
0.20
Griddle
Main Burner
Ø 2.10 mm
Ø 1.30 mm
Pilot Burner
0.35
0.23
Main Burner
Ø 2.60 mm
Ø 1.60 mm
Pilot Burner
0.35
0.23
Low Fire
Ø 1.5 mm
Ø 0.95 mm
Supply Pressure
1.13 - 3.40 kPa
2.75 - 4.50 kPa
Operating Pressure
0.95 kPa (*)
2.6 kPa (*)
Gas Regulator Cap Screw
Oven
Burner Aeration Setting
Fully Open
Fully Open
Burner Aeration Setting
Fully Open
Fully Open
Natural. Gas (G20)
Propane (G31)
Open Burner
Main Burner Injectors
Ø 2.30 mm
Ø 1.40 mm
Pilot Burner ('PF' Models Only)
0.30
0.20
Griddle
Main Burner
Ø 2.10 mm
Ø 1.30 mm
Pilot Burner
0.35
0.23
Main Burner
Ø 2.60 mm
Ø 1.60 mm
Pilot Burner
0.35
0.23
Low Fire
Ø 1.5 mm
Ø 0.95 mm
Supply Pressure
20 mbar
30 / 37 mbar
Operating Pressure
9.5 mbar (*)
26 mbar (*)
Gas Regulator Cap Screw
Oven
Burner Aeration Setting
Fully Open
Fully Open
Burner Aeration Setting
Fully Open
Fully Open