Gas Conversion and Specifications
23
Gas Specifications
- Australia:
- New Zealand:
(*)
Measure Burner operating pressure at target top hob manifold test point with target top
burner (Inner and outer ring) operating at full setting. Operating pressure is ex-factory set,
through appliance regulator and is not to be adjusted, apart from when carrying out gas
conversion, if required. (Refer to details in ’Gas Conversion’ section for information).
Natural Gas
LP Gas (Propane)
Main Burner Injector (Inner Ring)
Ø 1.70mm
Ø 1.10mm
Main Burner Injector (Outer Ring)
Ø 2.60mm
Ø 1.55mm
Pilot Burner Injector
0.35 0.25
Burner Aeration Screw X (Inner)
25mm 25mm
Burner Aeration Screw Y (Outer)
28mm 28mm
Low Fire Adjustment
2
1
/
2
turns out (ccw)
1 turn out (ccw)
Burner Operating Pressure (*)
1.0 kPa
2.6 kPa
Gas Regulator Cap Screw
Natural Gas
LP Gas
Main Burner Injector (Inner Ring)
Ø 1.70mm
Ø 1.10mm
Main Burner Injector (Outer Ring)
Ø 2.60mm
Ø 1.55mm
Pilot Burner Injector
0.35 0.25
Burner Aeration Screw X (Inner)
25mm 25mm
Burner Aeration Screw Y (Outer)
28mm 28mm
Low Fire Adjustment
2
1
/
2
turns out (ccw)
1 turn out (ccw)
Burner Operating Pressure (*)
1.0 kPa
2.6 kPa
Gas Regulator Cap Screw