WDIS410 or WDS100 or WDS600 or W900
The sensor is provided with a 2-twisted pair, shielded, 24 AWG, 35 pF/foot
capacitance cable. The wiring to the controller is as follows:
Shield
Drain:
Earth Ground
GRN:
IN+
WHT:
IN-
RED:
+5 V
BLK:
- 5 V
If the required cable length exceeds the 6 meters (20 feet) that is supplied,
wire the housing to a 190851 terminal box, then use a p/n 100084 cable to
reach the instrument. The maximum cable length is 30.5 meters (100 feet).
The optional flow switch is wired to one of the digital inputs as follows:
BLK:
DIG IN+
BLU:
DIG IN-
BRN:
+9 VDC