WBL Variables and their Limits
Low Limit
High Limit
Conductivity menu
PPM Conversion Factor 0.200 ppm/µS/cm 1.000
ppm/µS/cm
Interval Time (sampling) 5 minutes
24:00 hours
Duration Time (sampling) 1 minute
59 min: 59 sec
% Calibration Range -50
+50
Temperature Menu
No variables
BlowdownMenu
Set Point 0 µS/cm
10,000 µS/cm
Dead Band 5 µS/cm
500 µS/cm
Blowdown Limit Time (set in hours/minutes) 1 minute
8 hrs: 20 min
(enabled)
0=unlimited (disabled)
Feed Menu
Feed Lockout Timer (Mode A) 1 second
99 min: 59 sec
Percent of Blowdown (Mode B) 5 %
99 %
Feed Time Limit (Mode B) 1 minute
99 min: 59 sec
Percent of Time (Mode C) 0.1 %
99 %
Feed Cycle Time (Mode C) 10 minutes
59 min: 59 sec
Time per Contact (Mode D) 1 second
59 min: 59 sec
÷ Contacts by (Mode D) 1 contact
100 contacts
Time Limit (Mode D & E) 1 minute
99 min: 59 sec
Time/Vol (Mode E) 1 second
59 min: 59 sec
Vol to Initiate Feed (Mode E) 1
9,999
K Factor (Mode E) 1 pulse/vol
20,000 pulses/vol
4-20 mA Menu
4 & 20 mA Settings
0 µS/cm
10,000 µS/cm
Access Code Menu
New Value
0 9999
Alarm Menu*
High & Low (set to zero to disable)
1% 50%
Datalog Menu (Optional)
No variables
Config Menu (Optional)
No variables
Upgrade Menu
No variables
*Note: The Alarm relay is non-programmable. Refer to the Main Menu diagram on page 16 for the list of error
conditions that trigger the alarm relay.