212 Fieldbus Communication
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
11.3.5.14 Discrete Input Point Extended 1 (69
hex
)
The extension of the “Discrete Input Point” class enables the reading of data from
a fieldbus node that contains over 255 digital input points (DIPs). The instance
scope of the “Discrete Input Point Extended 1” class covers DIPs from 256 to 510
in the fieldbus node.
Instance 0 (Class Attributes)
Table 204: Discrete Input Point Extended 1(69 hex,) – Class
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance UINT
Max. number of instances
-
Instance 256 ... 510 (Digital input value 256 up to 510)
Table 205: Discrete output point (66
hex
) – Instance 256...510
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
DipObj_Value
BYTE
Digital input
(only Bit 0 is valid)
-
Common Services
Table 206: Discrete Input Point Extended 1 (69
hex
) – Common service
Service
code
Service available
Service-name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
11.3.5.15 Discrete Input Point Extended 2 (6D
hex
)
The extension of the “Discrete Input Point” class enables the reading of data from
a fieldbus node that contains over 510 digital input points (DIPs). The instance
scope of the “Discrete Input Point Extended 2” class covers DIPs from 511 to 765
in the fieldbus node.
Instance 0 (Class Attributes)
Table 207: Discrete Input Point Extended 2 (6D hex) – Class
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-