WAGO-I/O-SYSTEM 750 XTR
Fieldbus Communication 197
750-352/040-000 FC ETHERNET G3 XTR
Manual
Version 1.3.0
Static Assembly Instances – Overview
Table 175: Static assembly instances – Overview
Instance
Description
Instance 101 (65
hex
) for analog and digital output data
Instance 102 (66
hex
) for digital output data
Instance 103 (67
hex
) for analog output data
Instance 104 (68
hex
) for analog and digital input data and status
Instance 105 (69
hex
) for digital input data and status
Instance 106 (6A
hex
) for analog input data and status
Instance 107 (6B
hex
) for analog and digital input data
Instance 108 (6C
hex
) for digital input data
Instance 109 (6D
hex
) for analog input data
Instance 0 (Class Attributes)
Table 176: Assembly (04
hex
) – Class
Attribute ID Access Name
Data type
Description
Default value
1
Get
Revision UINT
Revision of this object
2 (0x0002)
Instance 101 (65
hex
)
This assembly instance contains analog and digital output data.
Table 177: Static assembly instances – Instance 101 (65
hex
)
Attribute ID Access Name Data type
Description
Default value
3
Get/Set Data
ARRAY of BYTE
Reference on the process
image: analog and digital
output data
-
Instance 102 (66
hex
)
This assembly instance contains digital output data only.
Table 178: Static assembly instances – Instance 102 (66
hex
)
Attribute ID Access Name Data type
Description
Default value
3
Get/Set Data
ARRAY of BYTE
Reference on the process
image: only digital output data
-
Instance 103 (67
hex
)
This assembly instance contains analog output data only.
Table 179: Static assembly instances – Instance 103 (67
hex
)
Attribute ID Access Name Data type
Description
Default value
3
Get/Set Data
ARRAY of BYTE
Reference of the process
image: only analog output
data
-