14
Device Description
WAGO-I/O-SYSTEM 750
750-506 2DO 24V DC 0.5A/ diagnostics
Manual
Version 1.2.0
Pos: 20.14 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hinweise/Achtung/Achtung: Maxi maler Str om Leistungskontakte 10 A @ 3\mod_1226499143500_21.docx @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos: 20.15 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Funkti on/Funktion 750-0506 Fehler bits @ 5\mod_1246963630232_21.docx @ 36732 @ @ 1
In the event of an overload, short circuit or line break, two error bits per channel
(bit 0 and 1 for channel DO 1, bit 2 and 3 for channel DO 2) are set in the input
process image as 2-bit error code. Using this bit pattern, the master control can
decrypt the error code and identify the error. After rectifying the error, the error
bits are reset in the input image and the red error LED goes off.
Pos: 20.16 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Gal vanische Trennung F eld/System @ 3\mod_1233756478750_21.docx @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos: 20.17 /Serie 750 ( WAGO-I/O-SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hinweise/War nungWarnung: Ei nsatz Variante /xxx- 8xx in sicherheitsg erichteten Anwendung en @ 5\mod_1246882860453_21.docx @ 36680 @ @ 1
Using in safety related applications!
When using the I/O module ( 750-506 ) in safety-related applications, the
instructions and connection examples in Section “Using Interference-Free
Variants of I/O Modules in Safety Related Applications” are to be observed!
Pos: 20.18 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Versorgung/Anordnung bei Einsatz in sicher heitsgerichteten Anwendungen bl ockweise @ 5\mod_1246876694406_21.docx @ 36674 @ @ 1
Any configuration of the output modules is possible when designing the fieldbus
node. Grouping of module types is not necessary.
Pos: 20.19 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ei nleitung/Einsatzbereich/Einsatzbereich 750- xxxx alle Koppler/C ontroll er ohne Ei nschränkung @ 3\mod_1232541691906_21.docx @ 26522 @ @ 1
The I/O module 750-506 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Pos: 21 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1