8 •
750-424 [2 DI DC 24 V, Intruder Detection]
Display Elements
WAGO-I/O-SYSTEM
750
I/O
Modules
The field side supply voltage of 24V for the input module is derived from
adjacent I/O modules or from a supply module
.
The supply voltage for the
field side is made automatically through the individual I/O modules by means
of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must be
added.
The digital input module 750-424 can be used with all couplers/controllers of
the WAGO-I/O-SYSTEM 750.
2.1.1.3 Display
Elements
LED
Channel Designa
tion
Contact
Closed
Contact
Open
short
Circuit
broken
Wire
A
green
Status
DI 1
on off on off
B
red
1
Error
DI 1
off off on
on
C
green
Status
DI 2
on off on off
13 14
C
D
B
A
D
C
B
A
Fig. 2.1.1-2: Display
Elements
g041802x
D
red
2
Error
DI 2
off off on
on
2.1.1.4 Schematic
Diagram
DI 1
DI 2
24V
0V
DI
0V
10nF
270 pF
Error
10nF
24V
Status
Uref1
Uref2
Uref3
1
2
3
4
5
6
7
8
750-424
Fig. 2.1.1-3: Intruder Detection 750-424