WAGO-I/O-SYSTEM 750
PROFIBUS Master in CoDeSys 2.3 145
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
DP Parameters
Figure 70: "DP Parameters" tab
The following table explains the parameters listed in the register:
Table 63: Description of the Parameters
DP Parameters
Info
Information on the manufacturer-specific GSD file.
Identification
Station address
Station name
Enter the station address of the slave here that is set on the DIP
switch.
Station name from the GSD file.
Activation
Slave active in current
configuration
Here, indicate whether the slave is to be parameterized and
configured.
GSD file …
Detailed information on the GSD file.
Standard parameters
Ident number
TSDR (TBit)
Lock/Unlock
Information from GSD file.
The values are automatically taken over from the GSD file.
Function is not currently supported.
Watchdog
Watchdog Control
Time (ms)
The Watchdog is activated if the control field is activated.
Here, enter the waiting time within which the master must
receive a signal before a replacement value is triggered for the
I/O modules. Set this replacement value using the interface
[Properties]
on the "Inputs/Outputs" tab.