I/O modules • 231
SSI transmitter interface 750-630
Modular I/O System
ETHERNET TCP/IP
Technical Data:
Item-No.:
750-630
750-630/000-
001
750-630/000-
006
Encoder connections
Data Input: D+; D-; Clock output: CI+; CI-
current consumption (internal)
85 mA typ.
Power supply
DC 24 V (-15%/+20%)
Sensor power supply
DC 24 V via power jumper contacts
Baud rate
max. 1 MHz
Data field width
32 Bit
Signal output (clock)
Differential signal (RS 422)
Signal input (positional)
Differential signal (RS 422)
Output data format
Gray code / Dual code
Internal bit width
1 x 32 Bit Data, 1 x 8 Bit control/status
Configuration
none, or via software with the consent of WAGO
Isolation
500 V system / power supply
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
Presetting
125 kHz
Gray code
24 Bit Data
125 kHz
Binary
24 Bit Data
250 kHz
Gray code
24 Bit Data
Terminal Configuration:
Input
Type
Function
Signal D+ and
Signal D-
Input, RS422
Positional data from encoder, Gray code
Signal Cl+ and
Signal CL-
Output, RS422
Clock signal output for communications interface
+24V
Input
24 V DC supply voltage to module, field connection.
0V
Input
0 V DC supply voltage return to module, field connection.
The use of this module in conjunction with a SSI encoder provides direct po-
sitional information rather than the type of data resulting from incremental ty-
pe encoders.
Absolute encoders are comprised of several data disks to generate a data word
which is unique through out the 360 degrees of rotation. The data format is a
modified binary pattern in either Gray code or Dualcode.
Содержание I/O-SYSTEM 750