60 Process Image
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
5.4.1
AC Measured Value Collection (010)
In the output data of the I/O module, the collection is selected via the COL_ID,
and 4 different measured values are selected from this collection via the
MET_IDs. The corresponding measured values are then made available in the
input data. After this, 4 other measured values can be selected, and so on.
Byte Output Data
Input Data
0 0x00
0x44
1 0x02 (status query)
0x02
2 0x00
0x40
3 0x0A (COL_ID)
0x0A (COL_ID_SEL)
4 0x06 (MET_ID_1)
0x06 (MET_ID_1_SEL)
5 0x03 (MET_ID_2)
0x03 (MET_ID_2_SEL)
6 0x4E (MET_ID_3)
0x4E (MET_ID_3_SEL)
7 0x17 (MET_ID_4)
0x17 (MET_ID_4_SEL)
8 ---
RMS voltage, L3-N [7:0]
9 ---
RMS voltage, L3-N [15:8]
10 ---
RMS voltage, L3-N [23:16]
11 ---
RMS voltage, L3-N [31:24]
12 ---
RMS current, L3 [7:0]
13 ---
RMS current, L3 [15:8]
14 ---
RMS current, L3 [23:16]
15 ---
RMS current, L3 [31:24]
16 ---
Reactive energy, L3 [7:0]
17 ---
Reactive energy, L3 [15:8]
18 ---
Reactive energy, L3 [23:16]
19 ---
Reactive energy, L3 [31:24]
20 ---
cos phi, L2 [7:0]
21 ---
cos phi, L2 [15:8]
22 ---
cos phi, L2 [23:16]
23 ---
cos phi, L2 [31:24]
In example 2, the status query is made for phase L3. The status word (Byte 0) is
at 0x44; an error has occurred at phase L3 (ERROR, ERR_L3). Byte 2 is at 0x40,
i.e. overvoltage at phase L3. The parameterized threshold value has been
exceeded.