18
Device Description
WAGO-I/O-SYSTEM 750
753-501 2DO 24V DC 0,5A
Manual
Version 1.2.0
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
3.2.3
CAGE CLAMP
®
Connectors
Depiction of the I/O module with 753-110 Connector!
Information on this pluggable connection pertains to the 753-110 Connector,
which is not included with the I/O module.
Figure 4: CAGE CLAMP
®
Connectors
Table 6: Legend for Figure “CAGE CLAMP
®
Connectors”
Channel Designation
Connector Function
1
DO 1
1
Output DO 1: Signal voltage
24 V
2
Output DO 1: Field supply
0 V
3
Output DO 1: Field supply
Ground
4
Output DO 1: Ground
2
DO 2
5
Output DO 2: Signal voltage
24 V
6
Output DO 2: Field supply
0 V
7
Output DO 2: Field supply
Ground
8
Output DO 2: Ground