WAGO-I/O-SYSTEM 750
Connect Devices
87
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Figure 43: Connection variant with 2 diode recovery circuits
In the output configuration H-Side/L-ide 2, you can connect an inductive load
between connection O1B to the common (ground) connection of the field supply
voltage 0V and/or a second inductive load between connection O2A to the
positive connection of the field supply voltage 24V.
In this case, pay attention to the voltage values listed in the table when selecting
the external diode recovery circuit.
Table 25: Maximum negative voltage of the diode recovery circuit, output configuration H-Side/L-
Side 2
Field Voltage
ULx
+19.2V
-31V
+24.0V
-26V
+26.4V
-24V
+28.8V
-21V
+31.2V
-19V