750-597 8AO 0-10V/±10V DC
Manual
Version 1.2.0
Table 27:
Scaling
Menu Item
Option
Description
Channel x
Enable manufacturer
scaling
Manufacturer scaling is enabled (no scaling of Gain and Offset).
*)
Manufacturer scaling is disabled (no scaling of Gain and Offset).
Gain
The Gain value is specified by the manufacturer.
Offset
The Offset value is specified by the manufacturer.
Enable user scaling
User scaling is enabled. By enabling this setting you can also
specify the individual gain and offset values.
*)
User scaling is disabled. Individually specified gain and offset
values cannot be entered.
Gain
Enter the Gain value for the user scaling.
The Gain value is used as a gain factor on the process value.
The resolution is 1/1024.
The value entered must fall in the value range of 0
… 63999.
Offset
Enter the Offset value for the user scaling.
The Offset value causes a zero offset of the process value (shift
along the Y axis).
The resolution is 1 mV per digit.
The value entered must fall in the value range of
−32768 … 32767.
Process value (hex)
Display of the process value for the channel selected in hexadecimal
notation.
The process value is read cyclically from the I/O module.
Voltage [V]
Display of the scaled expected voltage output value.
The expected voltage output value is read cyclically from the I/O module.
*)
Factory setting