74
Process Image
WAGO-SPEEDWAY 767
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
8.4
DIO Mode + 1 Counter
8.4.1
Input Data
The image for the process data, which are transmitted from the I/O module to the
fieldbus coupler, has a size of 4 bytes. If you configure synchronous diagnostic
data for the I/O module, the process image has a size of 6 bytes.
The byte configuration is as follows:
Table 44: DIO + 1 counter, input data in the process image
Byte 0 7
0
Digital inputs (process data)
\
-------------------
\/
-------------------
/
1
B
: Input value = True
State of the outputs is also displayed!
Byte 1 7
0
Counter status
\
-------------------
\/
-------------------
/
1
B
: See section “Counter Function”.
Byte 2 15
8
Counter value
\
-------------------
\/
-------------------
/
8 bits data. See section “Counter Function”.
Byte 3 7
0
Counter value
\
-------------------
\/
-------------------
/
8 bits data. See section “Counter Function”.
Byte 4 7
0
Diagnostic message
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1
| | | | | | 1
B
: Overtemperature on channel 2
| | | | | 1
B
: Overtemperature on channel 3
| | | | 1
B
: Overtemperature on channel 4
| | | 1
B
: Overtemperature on channel 5
| | 1
B
: Overtemperature on channel 6
| 1
B
: Overtemperature on channel 7
1
B
: Overtemperature on channel 8