To connect the supply cable to the fieldbus coupler and I/O modules, proceed as
follows:
1. Disconnect the power supply from those devices on which you have
mounted the module.
2.
For example, if on I/O module and this 2-A module have been connected to
the fieldbus coupler, connect the power supply transmission cable (K1) to
the associated IN and OUT connections, as shown in the following figure.
Retransmission of power supply not possible!
Because of the 2-A module's increased output current of 2 A for each channel,
retransmission of the power supply is not possible. It has two IN connections as a
result of the increased power requirement. For subsequent modules, the power
supply must therefore be newly fed.
3. Use the two IN connections (K2, K3) to supply power for the 2-A module,
as shown in the following figure.
4. Tighten the plugs and sockets using the knurled-head screws.
5.
Screw a protective cap on all unused ports to ensure that IP 67 degree of
protection is provided.
Information on connecting the power supply cable (K0) to the "IN" port (6) of
a fieldbus coupler can be found in the appropriate manuals.
Pos: 23.19 /Serie 767 ( WAGO-SPEED WAY)/Anschluss D aten- und Versorgungskabel/I/O-M odule/Anschluss_Spannungsversorgung 767- 4803 - Bild @ 5\mod_1249298502609_21.docx @ 40032 @ @ 1
Figure 16: Supply cable connected to the fieldbus coupler, I/O module and 2-A module
Pos: 23.20 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1