765-1503/100-000
Functions
28
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
Table 24: Overview of Parameterization Tools
Tool
Description
Controller with EtherNet/IP
scanner
The
EtherNet/IP scanner
must be configured to exchange process data with the
765 Series modules. The EDS file
wago_0765150x.eds
(x = 1 ... 5) describes a
WAGO I/O System Field module. The configuration software of the EtherNet/IP
scanner can import this EDS file.
The user can configure and parameterize a 765 Series module. The user loads the
configuration onto the EtherNet/IP scanner. The EtherNet/IP scanner configures
the 765 Series module via EtherNet/IP. Whether or not the scanner sends port
configuration parameters depends on the connection selected.
For example, if connection 1 is used, the EtherNet/IP scanner transfers parameters
to the 765 Series module.
For example, if connection 2 is used, the EtherNet/IP scanner transfers no param-
eters to the 765 Series module, and the port must be configured with a different
tool.
8
explains which connection causes EtherNet/IP scanner param-
eters to be transferred and which does not.
WAGO I/O Field Web-
server
The
WAGO I/O Field Webserver
is a Webserver that is integrated into the 765
Series module. With a Web browser, users can view the Web pages and display
and modify parameters.
WAGO I/O Field App
The
WAGO I/O Field app
is an app for mobile devices that can communicate with
a 765 Series module via Bluetooth
®
. With the app, the user can parameterize the
765 Series module, read and write process data and display diagnostics.
WAGO IO-Link Configura-
tor
WAGO IO-Link Configurator
is software for configuring the WAGO IO-Link mas-
ters and the IO-Link devices.
A distinction is made between two parts of the configuration and parameterization:
1.
EtherNet/IP configuration
: select EtherNet/IP connection
2.
Port configuration
: digital input or output
The following table shows which tool can influence which section.
Table 25: Parameterization Overview
Tool
EtherNet/IP Connection
Port Configuration
EtherNet/IP Scanner
The EtherNet/IP scanner
configures the EtherNet/IP
connection of the 765
module.
Whether or not the EtherNet/IP scanner transfers pa-
rameters depends on which connection is used.
Connection with parameterization: The scanner sets
the parameters selected by the user on the basis of
the parameters in the EDS file. These parameters con-
figure each individual port and determine whether the
port is used as a digital input or digital output (or is dis-
abled).
Connection without parameterization: A different tool
must be used to configure the port.
8
causes EtherNet/IP scanner parameters to be trans-
ferred and which does not.
WAGO I/O Field Web-
server
–
Yes
WAGO I/O Field App
–
Yes
WAGO IO-Link Configura-
tor
–
Yes