765-1205/100-000
Commissioning
Product manual | Version: 2.0.0
79
8DIO FLD EC DC 24V 2.0A
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > PortXX > Configuration
The following table lists port-specific configuration parameters.
Table 46: Port-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
OverCurrentPin1
Variable
Read
0
Warning level for current upper limit on pin 1;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin2
Variable
Read
0
Warning level for current upper limit on pin 2;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin4
Variable
Read
0
Warning level for current upper limit on pin 4;
unit: 1 mA
0: monitoring not enabled
UnderCurrentPin1
Variable
Read
0
Warning level for current lower limit on pin 1; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin2
Variable
Read
0
Warning level for current lower limit on pin 2; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin4
Variable
Read
0
Warning level for current lower limit on pin 4; unit:
1 mA
0: monitoring not enabled
10.3.3.1.4 Reading Port Process Values
The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 4 of a port in the
Pin4ProcessData
node.
Process Data of the Digital Inputs and Outputs
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > SIOProcessData
Note
OPC UA client can only read process output data
The process output data is written by the EtherCAT controller. The OPC UA client can
only read process output data.
The following table lists port-specific process data of the digital inputs and outputs.
Table 47: Port-Specific Process Data of the Digital Inputs and Outputs
Node Name
Node Class
Access
Description
Pin2ProcessData
Variable
Read
Process data on pin 2
Pin4ProcessData
Variable
Read
Process data on pin 4