765-1205/0100-0000
Properties
22
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
Please note the derating for use of the product. The surrounding air temperature and the
current affect the product’s heat generation.
The derating curve was created with the following conditions of use: “without air move-
ment and with 0.5 m/s air movement” and “mounting on wall with poor heat conductivity.”
The real conditions of use may lead to better heat dissipation from the product, e.g. due
to greater air movement or better dissipation of heat to the mounting wall. The product
provides measured values for temperature and current, which you can display with
WAGO Webserver I/O Field or read out via OPC UA.
The following figure shows the maximum permissible current (I) that can flow into the
product as a function of the surrounding air temperature (T).
15
20
25
30
20
T
[°C]
25
30
35
40
45
50
55
60
65
70
I
[A]
0,5 m/s
0 m/s
Figure 3: Derating, 0765-1205/0100-0000
4.6 Regulations and Standards
The following regulations and standards were used in the development of the module:
Table 19: Standards and Regulations
Standard
Title
EN 61000-6-2
Electromagnetic compatibility (EMC) – Immunity for industrial en-
vironments
EN 61000-6-4
Electromagnetic compatibility (EMC) – Emission standard for in-
dustrial environments
EN 61131-2
Programmable logic controllers
IEC 61158
EtherCAT
®
IEC 60068-2-27 / 2008-02
Shock testing
IEC 60068-2-6 / 2007-12
Vibration testing (sinusoidal)
4.7 Approvals
The following approvals have been granted for the product:
Conformity marking
UL
UL 61010-1 and UL
61010-2-201, “Ordinary
Location”
In preparation.
Bluetooth
®
This module has an RF
transmitter with the follow-
ing specifications: