Touch Panel Advanced Line
Mounting 67
762-5xxx/8000-000x TP 600
Manual
Version 1.3.0
6.3
Mounting in Compliance with VESA Standard
No VESA mounting in the field of DNV GL applications!
If a DNV GL approval is required for your application you must install the panel
into cabinet resp. housing. Mounting in compliance with VESA standard is not
permitted!
The permitted ambient temperature depends on the mounting position!
If the panel is not installed vertically, cooling is affected, i.e., maximum
permissible ambient temperature is reduced. For exact values, see section
“Device Description” > “Technical Data”.
In addition to installation in a cutout, the panel can also be mounted, e.g., on a
monitor stand, via four M4×8 screws (strength rating: 8.8). To support this, four
threaded holes are drilled in a 75 × 75 mm square arrangement at the rear of the
panel in compliance with the VESA MIS-D 75 C standard. Because the panel is
unprotected when pole-mounted, it only has an IP20 degree of protection.
Insert the four screws 4 to 6 mm into the panel and torque to 3 Nm. Secure all
cables using strain reliefs and sufficient cable ties.