WAGO-TO-PASS® 761
Parameterizing
63
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
Manual
Version 1.0.0
7.5.2
Multiplex Input
You can configure digital inputs DI1 ... DI4 as multiplex inputs. These four inputs
will then additionally be read in as a combination and intepreted as a binary
number. The following applies in this case:
DI1 = 2
0
= 1,
DI2 = 2
1
= 2,
DI3 = 2
2
= 4 and
DI4 = 2
3
= 8.
Thus, for example, if DI1 and DI3 are set, then the binary number is 5. If only DI4
is set, then the binary number is 8.
In the multiplex table you can define an alarm message for each of the 16 statuses
(0 ... 15). The recipients of the messages can be selected using the multiplex
settings.
Counter inputs cannot be evaluated as multiplex inputs!
Counter inputs cannot be evaluated as multiplex inputs, as these inputs cannot be
set.