WAGO-I/O-SYSTEM 750
Service 133
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Manual
Version 1.0.0, valid from HW/SW Version 01/01
•
If the coding switch of the F I/O module to be replaced is set to 0 and it is
operated without iPar server functionality, continue reading in Section
“Service” > … > “PROFIsafe Address Set Using the Parameterization Tool.”
10.1.2
F I/O Module with iPar Server Functionality
10.1.2.1 PROFIsafe Address Set Using the Coding Switch
If the PROFIsafe address of the F I/O module to be replaced is set using the
coding switch on the side, i.e., the switch setting does not equal 0, proceed with
replacing the F I/O module as follows:
After start-up, the replacement module automatically requests its iParameters
from the iPar server. The safety-related verification of these parameters occurs in
the F I/O module. If the verification step is unsuccessful, the replacement module
sends a second request to the iPar server. If the process cannot be completed
successfully, the replacement module remains in its initial state and must be
configured using the WAGO parameterization tool (see Section “Commissioning”
>
… > “Parameterization of the F I/O Module with the WAGO Parameterization
Tool”).
10.1.2.2 PROFIsafe Address Set Using the Parameterization Tool
If the coding switch of the F I/O module to be replaced is set to 0, the PROFIsafe
address of the replacement module must be set through the parameterization
tool (see Section “Commissioning” > … > “Parameterization of the F I/O Module
with the WAGO Parameterization Tool"). After successfully setting the
PROFIsafe address, proceed as follows:
After start-up, the replacement module automatically requests its iParameters
from the iPar server. The safety-related verification of these parameters occurs in
the F I/O module. If the verification step is unsuccessful, the replacement module
sends a second request to the iPar server. If the process cannot be completed
successfully, the replacement module remains in its initial state and must be
configured using the WAGO parameterization tool (see Section “Commissioning”
>
… > “Parameterization of the F I/O Module with the WAGO Parameterization
Tool”).
10.1.3
F I/O Module without iPar Server Functionality
10.1.3.1 PROFIsafe Address Set Using the Coding Switch
If the PROFIsafe address of the F I/O module to be replaced is set using the
coding switch on the side, i.e., the switch setting does not equal 0, set the
replacement module identically to the F I/O module that was replaced. Then set
the parameters for the replacement I/O module using the WAGO
parameterization tool (see section “Commissioning” > … > “Parameterization of
the F I/O Module with the WAGO Parameterization Tool").