Table 55: RUN LED Diagnostics
Status
Explanation
Remedy
Red,
goes out longer
Cold start reset
completed
---
Red, flashing
At least one
application after in the
“STOP” status after
exception (e.g.,
memory access error)
Start the application with a reset via the
mode selector switch or in the connected
IDE.
If the application cannot be started,
restart the controller.
Contact WAGO Support if the error
occurs again.
Orange/green
flashing
Load above threshold
value 1
Try to reduce the load on the system:
- Change the CODESYS program.
- End any fieldbus communication that
is not essential, or reconfigure the
fieldbuses.
- Remove any non-critical tasks from
the RT area.
- Select a longer cycle time for IEC
tasks.
Orange
Runtime system in
debug state
(breakpoint, single
step, individual cycle)
Resume the application in the connected
IDE with single step or start.
Remove the breakpoint if necessary.
If the connection has been interrupted,
set the mode selector switch to “STOP”
and then back to “RUN” to enable the
application to continue
OFF
No runtime system
loaded
Enable a runtime system, e.g., via the
WBM.
10.1.2 Network Connection LED
10.1.2.1 “LNK ACT” LED
The “LNK ACT” LED indicates following diagnostics:
Table 56: “LNK ACT” LED Diagnostics
Status
Explanation
Remedy
Off
No network
communication via
port
Check network connections and network
settings.
Green
Connection to the
physical network
available
---
Green flashing Network
communication via
port