110 e!RUNTIME Runtime Environment
WAGO I/O System Compact
751-9301 Compact Controller 100
Manual
Version 1.1.0, valid from FW Version 03.08.07(20)
9.4.3
Analog Temperature Inputs
The analog temperature sensor inputs PT1+ / PT1– and PT2+ / PT2– are
represented at a resolution of 1 digit per 0.1
°C via the INT data type (16 bit).
Table 51: Process Image – Analog Temperature Inputs
Chan-
nel
Pin
Data
Type
Mea-
sured
Value
Value Range
Hex.
Dec.
Bin.
PT1+ /
PT1–
X13.1 /
X13.2
INT
–60
°C
…
350
°C
0xFDA8*
…
0x0DAC
–600
…
3500
1111.1101.
1010.1000*
…
0000.1101.
1010.1100
PT2+ /
PT2–
X13.3 /
X13.4
>
350
°C
0x0DAC
3500
0000.1101.
1010.1100
*
Temperature values below 0 °C are
represented in two's complement binary and
hexadecimal.
9.4.4
Digital Inputs
The digital inputs DI1 … DI8 are represented per channel via the BOOL data
type. In addition, the digital inputs are represented via the BYTE data type.
Table 52: Process Image – Digital Inputs
Chan-
nel
Pin
Data
Type
Mea-
sured
Value
Value Range
Hex.
Dec.
Bin.
DI [1
…
8]
X12
BYTE
0 /
+24 V
DC
0x00
…
0xFF
0
…
255
0000.0000
…
1111.1111
DI1
X12.3
BOOL
–
–
TRUE /
FALSE
DI2
X12.4
DI3
X12.5
DI4
X12.6
DI5
X12.7
DI6
X12.8
DI7
X12.9
DI8
X12.10
9.4.5
Digital Outputs
The digital outputs DO1 … DO4 are represented per channel via the BOOL data