10
•
751-4501 [AS-Interface Module 4OUT 24V/2A Single]
Display
Elements
WAGO-I/O-SYSTEM
751
AS-Interface Components IP20
Warning
The unused connectors X5 ... X8 are DC coupled with the AS-Interface
voltage. They shall not be connected externally!
Warning
Connectors must only be mated or unmated in “No Load” condition!
2.1.1.3.3 Programming Connector
On the left side of the front plate is the programming connector. It is a plug for
a DC socket which is compatible with all popular programming adapters, for
example Fuchs VAZ-PK-1.5M-V1-G.
Please note manufacturer documentation for the operation of the programming
device..
2.1.1.4 Display Elements
Tab. 2.1.1-3: Display Elements
LED
Designation
Status
Function
off
Output 1, reset
O1
yellow
Status
DO1
on
Output 1, set
off
Output 2, reset
O2
yellow
Status
DO2
on
Output 2, set
off
Output 3, reset
O3
yellow
Status
DO3
on
Output 3, set
off
Output 4, reset
O4
yellow
Status
DO4
on
Output 4, set
off OK
on Configuration
error
FLT
red
Error
blinking
Short circuit / sensor
supply overload or actuator
supply is missing or output
driver error message
(Open-Load-Detection)
off
AS-Interface supply error
ASI
green
AS-Interface
supply
on
AS-Interface supply OK
off
Actuator supply error
O3
O1
O4
O2
FLT ASI
AUX
Fig. 2.1.1-4: Display
Elements
gq45012x
AUX
green
Actuator
supply
on
Actuator supply OK
2.1.1.5 Operating Elements
The AS-Interface module 751-4501 has no operating elements.