Climatic environmental conditions
Table 23: Technical Data - Climatic environmental conditions
Operating temperature range
0 °C ... 55 °C
Operating temperature range for
components with extended
temperature range (750-xxx/025-xxx)
-20 °C ... +60 °C
Storage temperature range
-20 °C ... +85 °C
Relative humidity
max. 5 % ... 95 % without condensation
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75%
SO
2
25 ppm
H
2
S
10 ppm
Special conditions
Ensure that additional measures for
components are
taken, which are used in an environment
involving:
– dust, caustic vapors or gases
– ionization radiation
Pos: 43.4 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung/Technische Daten/Feldbuskoppler/-controller/Achtung: Verringerte Pufferzeit bei zu hoher Lagertemperatur! (bei Echtzeituhr) @ 8\mod_1278604366911_21.doc @ 59412 @ @ 1
NOTICE
Reduced buffer time at high storage temperature!
Ensure that the storage of devices with a real time clock at high temperatures
leads to a reduced buffer time for the real time clock.