Fieldbus Communication
•
183
EtherNet/IP (Ethernet/Industrial Protocol)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
4.3.3.2.4 Identity (01
hex
)
Class
Attribute
ID
Access Name
Data
type
Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Maximum Instance
0x0001
3
Get
Max ID Number
of Class
Attributes
UINT
Maximum number of Class
attributes
0x0000
4
Get
Max ID Number
of Instance
Attribute
UINT
Maximum number of instance
attributes
0x0000
Instance 1
Attribute
ID
Access
Name
Data type
Description
Default value
1
Get
Vendor ID
UINT
Manufacturer identification
40 (0x0028)
2 Get
Device Type
UINT
General type designation of
the product
12 (0x000C)
3 Get
Product Code
UINT
Designation of the controller e.g. 841 (0x0349)
for the controller
750-841
Revision STRUCT
of:
Major Revision
USINT
4 Get
Minor Revision
USINT
Revision of the Identity
Objects
Depending on the
firmware
5
Get
Status
WORD
Current status of the device
Bit 0: Assignment to
a master
Bit 1=0 (reserved)
Bit 2: Configured:
(=0: Configuration
is unchanged;
=1: Configuration
is different to the
manufacturers
parameters)
Bit 3=0 (reserved)
Bit 4-7: Extended
Device Status:
(=0010: at least one
faulted I/O
connection,
=0011: no I/O
connection
established)
Bit 8-11: not used
Bit 12-15=0
(reserved)
6
Get
Serial Number
UDINT
Serial number
The last 4 digits of
MAC ID
7 Get
Product
Name
SHORT_STRING
Product name
e.g. “WAGO
Ethernet (10/100
Mbps)-FBC