WAGO-I/O-SYSTEM 750
Appendix 353
750-8207 PFC200 CS 2ETH RS 3G
Manual
Draft version 1.2.1 from 2017-09-13, valid from FW Version 02.06.20(09)
15.1.3 Analog Input Modules
The analog input modules provide 16-bit measured data and 8 control/status bits
per channel.
The controller only uses the 8 control/status bits internally for
configuration/parameterization (e.g., via WAGO-I/O-
CHECK
).
Therefore, only the 16-bit measurement values for each channel are in Intel
format and are mapped by word in the input process image for the controller.
When digital input modules are also present in the node, the analog input data is
always mapped into the Input Process Image in front of the digital data.
Information on the structure of control and status bytes
For detailed information on the structure of a particular I/O module’s
control/status bytes, please refer to that module’s manual. Manuals for each
module can be found on the Internet at
15.1.3.1 1 Channel Analog Input Modules
750-491, (and all variations)
Table 260: 1 Channel Analog Input Modules
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
D1
D0
Measured Value U
D
1
D3
D2
Measured Value U
ref
15.1.3.2 2 Channel Analog Input Modules
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, 476, -
477, -478, -479, -480, -481, -483, -485, -492, (and all variations),
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, 476, -477,
478, -479, -483, -492, (and all variations)
Table 261: 2 Channel Analog Input Modules
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
D1
D0
Measured Value Channel 1
1
D3
D2
Measured Value Channel 2