WAGO I/O SYSTEM 750 XTR
Run-time System CODESYS 2.3 249
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
8.2.5
Loading and Running the PLC Program in the Fieldbus
Controller (ETHERNET)
Requirement:
•
The simulation is deactivated (
Online > Simulation
).
•
The PC is linked to the controller via ETHERNET. Refer to Section “Device
Description” > …> “ETHERNET – X1, X2 Network Connection”.
Proceed as follows:
1.
In the menu bar click on
Online
and select
Communication parameters
…
. The “Communication Parameters” window opens.
2.
To select a communication link click on
[New …]
in the “Communication
Parameters” window. A window opens in which you can define a
communication link.
Figure 69: Creating a Communication Link – Step 1