18
•
750-641 [DALI/DSI Master Module]
Process
Data
WAGO-I/O-SYSTEM
750
I/O
Modules
Bit Control
byte
Status
byte
Function
0 TR
Transmit
Request
TA
Transmit
Accepted
Data direction control => module (DALI control commands).
Handshake for data transfer is completed via this bit. When
the state of TR (TA
TR) is changing, 5 data bytes are loaded
from the internal data bus into the internal module buffer.
When D4 = 0 (i.e. no command extension is available), the
data bytes D0 and D1 are stored in the DALI transmit buffer
gelegt. If D4 is unequal zero, the command interpreter will
have to execute a macro inducing the communication via the
DALI bus. This transmission (TA=TR) will be indicated by
the module via TA.
1 RA
Receive
Accepted
RR
Receive
Request
Data direction module => control (DALI requests)
Due to RR changing status (RA
RR), the module will advise
the control that it can provide 5 bytes for transmission. After
the transfer of data in the control byte has been aknowledged
by the control via RA (RA=RR), the new data can be
transmitted or received by the module.
2 IR
Init
Request
IA=0
Init
Accepted
Resetting the module into the default status.
The initialization is accomplished only with a rising edge.
The acknowledgement IA=1 persists so long, until a new
regular command over TR/TA is requested.
3
Actor
Error
Lamps or electronic ballasts‘ errors
4
Frame
Error
The TxD / RxD framing error is set in the event of an error
until the next error-free transmission.
5
Bus-Error The DALI bus error (collision, short circuit or open circuit)
may occur in a very short time. The consecutive error is often
a frame error. When a short-circuit of duration > 500ms is
detected by the module, the module sets the DALI voltage to
zero over a period of 5 seconds. Subsequently, the state
machine of the module will be set to an initial value.
Gen.
Error
General module errors, e.g. POST of the internal flash
memory, DALI bus error (lasting short-circuit or open
circuit), however no electronic ballasts‘ errors.
6
DALI
Active
The module supresses telegrams with the process value 0x00,
even if at the same time thereby the bit DALI Active is reset
of 1 to 0. For compatibility reasons however only the falling
edge is used for suppression.
7
always = 0